Revised the connection descriptions between the connection cable and circuit board in Figure 2. Replaced existing 22-pin MobileView Connection Cable table with a newer table. Replaced bullet-point text with table in The MobileView IP65 Junction Box section. Revised URL for Product Certifications website. 44, 47 Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
3-position, twin circuit, enabling switch for safety system interface • – Plug for alternate cable outlet not used (meets degree protection IP65) • – Back cover to access connection compartment (1) The 2711T-T10I1N1-TC MobileView terminal does not have this feature. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
ATTENTION: Personnel responsible for the application of safety-related Programmable Electronic Systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 5
MobileView 2711T terminal recognizes the dangerous situation and reacts in time to avoid the danger. Consider reduced speed of movements as a precautionary measure, which can be done through the risk assessment of machinery. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 6
Verify that machine or plant operation stops when the button is pushed. • When a second generation MobileView 2711T terminal has been exposed to shock (for example, it is dropped on the ground), test to verify that the E-stop push button still functions properly. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
3. Carefully lift off the back cover and set it aside. Figure 1 on page 8 shows the main circuit board of the second generation MobileView 2711T terminal with the back cover removed. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 8
For more information, see Figure 2 on page Use the following tools to install the 22-pin connection cable: • 19 mm open-end wrench or spanner • Torx T10 screwdriver • 8 mm hex key Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 9
4. If present, unscrew and remove the gray fitting from the connector-cable mounting assembly. 5. Unscrew the strain relief from the connector-cable mounting assembly to allow the red cable to slide freely. Connector-cable Mounting Assembly Strain Relief Gray Fitting Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 10
Torque the connector-cable mounting assembly to 1.2 N•m (10.6 lb•in). 12. If you chose left-hand operation, reinstall the plug in the open cable-connection port with an 8 mm hex key. Torque the plug to 1.2 N•m (10.6 lb•in). Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Consider the following before you mount an IP65 junction box: • Do not mount near a heat source or where direct sunlight is likely. • Do not mount where excessive mechanical vibrations, excessive dust, humidity, or strong magnetic fields are likely. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 13
Figure 3 - 2711T-JBBKCOVER Back Cover Plate Dimensions All dimensions are in mm (in.) 221.1 (8.7) 140 (5.51) (1.57) 162.1 (6.38) 132.5 (5.22) Mounting Holes, 172 (6.77) 4 x 4.5 (0.18) Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 14
M4 nuts. However, the fasteners depend on the material of the mounting surface, such as the wall of a control cabinet or a machine. 4. Attach the back plate to the mounting surface. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
2. Remove the cable glands from the cable outlets at the bottom of the junction box that you plan to use. 3. With a small flat head screwdriver, remove the black plugs from the seal rings that you plan to use. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 16
8. After all wires are attached, hand-tighten the cable glands to secure the wires. IMPORTANT To maintain the protection class, any unused cable outlet must be sealed with a black plug. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 17
6-pin terminal for an application or control system where multiple IP65 junction boxes are used. This terminal helps identify which IP65 junction box has a second generation MobileView terminal attached to it. For more details, S10 Terminal Pin Descriptions on page Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 18
The two Ethernet connectors on the IP65 junction box provide connection to an Ethernet network. Each connector uses an 8-pin, RJ45 modular jack connector. Pinouts are as follows. Pin # Ethernet Signal Pin # Ethernet Signal Not used Not used Not used Not used Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
BoxID Functionality on page ADJUST Use this switch to set the brightness of the illuminated E-stop button on a second generation MobileView terminal. For more details, see Illuminated E-stop Button Brightness on page Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 20
AID 1043633. Table 1 - Address Examples Left Address Right Address MobileView Left Address Right Address MobileView Switch Switch Terminal Address Switch Switch Terminal Address (1) Factory set as standard. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Figure 6 on page 19 for where to find the Box ID address switches on the junction box circuit board. page 20 for how to configure Box ID functionality for your 2711T-JBI65MI junction box. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Connector Description M12 Connector Type Ethernet I/O D-code pin female Dry contact 5 pin micro-style male Enabling device 5 pin I/O male Control power Mini 4 pin male E-stop 5 pin I/O male Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 23
E-stop 1 safe input Enabling device 1 safe input — E-stop 1 test output Enabling device 1 test output M12 Power Pin Descriptions Description Output power + Sensor/MDL power + Sensor/MDL power – Output power – Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Verify that the status indicator bar on the front of the IP65 junction box changes from solid red to solid yellow. b. Verify that the status indicator bar reduces one blinking yellow light after each 1.67 seconds of disconnect time. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
A second generation MobileView terminal with an illuminated E-stop button is connected E-stop to the junction box. No color A second generation MobileView terminal without an illuminated E-stop button is connected to the junction box. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 26
When power is restored, these saved states are subsequently retrieved. Therefore, the IP65 junction box can have the following states. State Description Normal A second generation MobileView terminal (with an unactivated E-stop push button) is connected. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 27
10 seconds triggered. (1) You must first configure an IP65 junction box to recognize an illuminated E-stop push button on a second generation MobileView terminal. For more information, see DIP Switch on page Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
The Ethernet connector on IP65 junction boxes provide a connection to an Ethernet network. The connector uses an 8-pin, RJ45 modular jack connector. To connect to an Ethernet network, see Ethernet (ETH3, ETH2) Connections on page Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
2. Check the second generation MobileView 2711T terminal for a start-up screen. Status Indicator Light Start-up Screen If the start-up screen does not appear, check the 24V DC power source and cable connections at the IP65 junction box and second generation MobileView 2711T terminal. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 30
4. Test the E-stop push button and the enabling switch to verify that each safety function is operating properly. Verify that the machine or plant operation stops when the button is pushed. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 31
When you touch a data field in a dialog box, an onscreen keyboard appears so that you can type in your information. You can also connect and use an external keyboard through the USB port on the back of the terminal. 2. After you add information, press Next. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 32
A license-terms dialog box appears. The license terms apply to Microsoft® Windows® Embedded Standard 7 operating system and all Allen-Bradley software content. 5. Press to check the ‘I accept the licensed terms’ box, and press Next. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 33
Second Generation MobileView Tethered Operator Terminal 6. Choose your appropriate date and time settings, and press Next. A pop-up dialog box appears, ‘Windows is finalizing your settings.’ When completed, the second generation MobileView 2711T terminal desktop appears. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 34
Rockwell Automation recommends that you only enable EWF after applications on the second generation MobileView 2711T terminal such as FactoryTalk® View Machine Edition (ME) have been set up.
Page 35
EWF is enabled. IMPORTANT Rockwell Automation recommends that you only enable EWF after applications on the second generation MobileView 2711T terminal such as FactoryTalk View ME software have been set up. If you make application changes with EWF enabled, then those changes are lost when the second generation MobileView 2711T terminal is powered down or rebooted.
Page 36
2. Touch and hold for about 3 seconds, and then release. A pull-down menu appears. 3. Press Properties. 4. On the Properties dialog box, press to select Internet Protocol Version 4 (TCP/IPv4). 5. Press Properties. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 37
To initially configure FactoryTalk View ME Station, perform the following steps. 1. Create a runtime application file (MER) with FactoryTalk View Studio software. 2. Within FactoryTalk View Studio software, launch the transfer utility. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 38
• Click Download (D). See the graphic with step 6 page 39 to view the MER file location on the SD card. 4. On the second generation MobileView 2711T terminal desktop, press FTView ME Station. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 39
FactoryTalk View ME Station to automatically start on a MobileView 2711T terminal power up or reboot). 10. If desired, press Application Settings or F3 to configure FactoryTalk View ME Station application-specific settings (for example, device shortcuts or start-up language). Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 40
For more information, see Enhanced Write Filter (EWF) on page To disable right-click touch screen functionality, perform the following steps. 1. From the second generation MobileView 2711T terminal desktop, press Touch Configuration. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Page 41
2. On the Touch tab of the Pen and Touch dialog box, press Press and hold. With Press and hold highlighted, press Settings. 3. Clear the Enable press and hold for right-clicking checkbox. 4. Press OK. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
1. Close FTView ME Station and return to the second generation MobileView terminal desktop. 2. Press on the desktop taskbar to shut down the second generation MobileView 2711T terminal. 3. Press OK on the shutdown confirmation dialog box. The terminal shuts down. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Second Generation MobileView Tethered Operator Terminal European Communities (EC) Directive Compliance Rockwell Automation hereby declares that second generation MobileView 2711T terminals with E-stop functionality are in conformity with Directive 2006/42/EC as specified in the Declaration of Conformity available from rok.auto/certifications.
(3) Reaction time is time before the E-stop is triggered. (4) Decommission the safety function once the E-stop has been activated 250,000 times or after 20 years, whichever comes first. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
2711T-22JUMP A black, 22-pin bridge connector to bypass E-stop contactors in an IP65 MobileView junction box. (1) For applications where the customer plans to move one MobileView terminal between many MobileView junction boxes. Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019...
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, FactoryTalk, Guardmaster, MobileView, On-Machine, Rockwell Automation, Rockwell Software, and ThinManager are trademarks of Rockwell Automation, Inc. Intel Atom is a trademark of Intel Corporation. Microsoft and Windows are trademarks of Microsoft Corporation.