PanelView 800 HMI Terminals
Catalog Numbers 2711R-T4T, 2711R-T7T, 2711R-T10T
User Manual
Original Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Allen-Bradley PanelView 800 and is the answer not in the manual?

Questions and answers

Summary of Contents for Rockwell Automation Allen-Bradley PanelView 800

  • Page 1 PanelView 800 HMI Terminals Catalog Numbers 2711R-T4T, 2711R-T7T, 2711R-T10T User Manual Original Instructions...
  • Page 2 Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in alignment with the movement toward inclusive language in technology. We are proactively collaborating with industry peers to find alternatives to such terms and making changes to our products and content.
  • Page 3: Table Of Contents

    Delete Fonts..........38 Change the Error Alert Display Settings ..... . . 39 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 4 Modbus RTU Communication ....... . 82 Modbus RTU Unsolicited Communication ..... 84 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 5 Transfer the Firmware to the Storage Device ....124 Install the Firmware from the Storage Device ....124 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 6 Change the Startup Application ......155 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 7 ............. . . 163 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 8 Table of Contents Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 9: Preface

    No special knowledge is required to understand this manual or operate the terminal. Equipment installers must be familiar with standard panel installation techniques. (a) The web browser feature is not supported on PanelView 800 terminals from firmware revision 3.011 onwards. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 10: Firmware Updates

    Contact your local Allen-Bradley® distributor or sales representative. • Go to the Rockwell Automation Product Compatibility and Download Center at rok.auto/pcdc. IMPORTANT You must sign in to the Rockwell Automation website before downloading a firmware revision. Additional Resources These documents contain additional information concerning related products from Rockwell Automation.
  • Page 11: Overview

    (a) The web browser feature is not supported on PanelView 800 terminals from firmware revision 3.011 onwards. (b) The PanelView Explorer feature is not supported on PanelView 800 terminals from firmware revision 3.011 onwards. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 12 USB device port (1) The Power status LED is red when in screen saver or dimmer mode and green when in normal (operational) mode. (2) The USB device port is not intended for Customer use. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 13: How To Connect Browser

    You can find the IP address on the terminal configuration screen under Communications. IMPORTANT The web browser feature is only supported on PanelView 800 terminals with firmware revision 2.020 or earlier. It is not supported from firmware revision 3.011 onwards. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 14: Usb Device Port

    This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 15: Catalog Number Configuration

    These are the available PanelView 800 terminals. Configuration Cat. No. Operator Input Size Display Type 2711R-T4T Touch screen and function keys 4 in. Color TFT 2711R-T7T Touch screen 7 in. Color TFT 2711R-T10T Touch screen 10 in. Color TFT Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 16 Chapter 1 Overview Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 17: Configure The Terminal

    Firefox browser Ethernet connectivity On Terminal Configuration (a) The web browser feature is not supported on PanelView 800 terminals from firmware revision 3.011 onwards. For more information about the PanelView Explorer feature, see Appendix Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 18: Configure Using The Terminal

    3.011 onwards. For more information about the PanelView Explorer feature, see Appendix (b) The VNC feature is only supported on PanelView 800 terminals with firmware revisions 4.011…7.011. For more information, contact your local technical support at rok.auto/phonesupport. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 19: Main Configuration Settings

    IMPORTANT At runtime, diagnostic messages appear in the same language as the application if the application language is English, Portuguese, French, Italian, German, Spanish, Chinese, or Korean. For all other languages, the diagnostic messages appear in the configuration language set on the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 20: Change The Date And Time

    Follow these steps to restart the terminal from the terminal. 1. Go to the main configuration screen. 2. Press Reset Terminal. 3. Press Yes to confirm. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 21: File Manager Settings

    2. Select Internal as the Source location of the application. 3. Select the location to copy the application from the To list, either USB or microSD card. 4. Select the name of the application from the Name list. 5. Press Copy. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 22: Import An Application

    IMPORTANT To perform a copy or edit operation on a recipe of an application, that application must be unloaded or not running. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 23 4. Select the location where you want to copy the recipe from, or copy the recipe to. 5. Select the recipe from the recipe list. 6. Press Copy. IMPORTANT Copying out a recipe from a design secured application is not allowed. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 24 IMPORTANT Renaming of a recipe in a design secured application is not allowed. 6. Press the blue area next to Name to change the name of the recipe. IMPORTANT Deletion of a recipe in a design secured application is not allowed. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 25: Copy Alarm History

    Follow these steps to copy the alarm history. 1. Go to the File Manager screen. 2. Use the up and down arrow keys to select the application that you want to copy the alarm history from. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 26: Change Controller Settings For An Application

    2. Press Controller Settings. Controller Settings Application Name: PV800_App1 Protocol: Ethernet | Allen-Bradley MicroLogix/ENI PLC-1 : 10.116.37.12 Type: MicroLogix 1400 Address: 10.116.37.12 Back 3. Press the blue area next to Address to change the address. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 27: Terminal Settings

    Adjust the Display Brightness • Calibrate the Touch Screen • Changing the Display Orientation • Configure Screen Saver Settings • Delete Fonts • Change the Error Alert Display Settings • Configure Print Settings Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 28: Change Ethernet Settings

    The terminal prompts an alert (ID: 2058) when you try to do Follow these steps to set a static IP address for the terminal’s Ethernet port from the terminal. 1. Go to the Terminal Settings screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 29 4. Press Set Static IP address screen appears. Static IP Address IP Address: 0.0.0.0 Mask: 0.0.0.0 Gateway: 0.0.0.0 Back 5. Press the blue area next to IP address to enter an IP address in the Static IP address field. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 30: Change Port Settings

    FTP Settings Gateway: 0.0.0.0 Back MAC Address: XX:XX:XX:XX:XX IMPORTANT The VNC feature is only supported on PanelView 800 terminals with firmware revisions 4.011…7.011. For more information, contact your local technical support at rok.auto/phonesupport. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 31: Enable The Ftp Server

    Protocol) client such as a web browser, PC file explorer, or third-party FTP software. This gives you read-only access to the Alarm History, Datalog, and Recipe folders on the terminal. To access the contents of these folders, Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 32 FTP Settings Gateway: 0.0.0.0 Back MAC Address: XX:XX:XX:XX:XX IMPORTANT The VNC feature is only supported on PanelView 800 terminals with firmware revisions 4.011…7.011. For more information, contact your local technical support at rok.auto/phonesupport. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 33: Adjust The Display Brightness

    2. Press Display. Display Brightness Calibrate Touchscreen Orientation (Requires Reset) 0 degrees Screen Saver Font Back 3. Use the arrow keys to adjust the brightness up or down. The change takes effect immediately. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 34: Calibrate The Touch Screen

    1 mm (0.040 in.) to help prevent damage to the touch screen. 1. With a stylus, tap the center of the target (+) on the terminal screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 35: Changing The Display Orientation

    You cannot change the display orientation from PanelView Explorer. If you want to change this setting, you must do so from the terminal configuration screens. Follow these steps to change the display orientation from the terminal. 1. Go to the Terminal Settings screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 36: Configure Screen Saver Settings

    1…60 minutes. The brightness intensity of the screen saver or dimmer can be adjusted between 0…100%. Follow these steps to configure the screen saver from the terminal. 1. Go to the Terminal Settings screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 37 Mode = Disable, Image, Dimmer, Image and Dimmer. 6. Select the brightness. Brightness 0…100, increments of 1. 7. Select the idle timeout. Choices are 1, 2, 5, 10, 15, 20, 30, or 60 min. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 38: Delete Fonts

    See Select a Terminal Language on page 19. The “Gulim” font will not appear in the Font screen and cannot be deleted unless you restore or return the terminal to out-of-box condition. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 39: Change The Error Alert Display Settings

    Only printers that use the PCL 5 protocol are supported. The actual print size depends on the size of the terminal, paper size, orientation, and stretch option. Follow these steps to configure the print settings. 1. Go to the Terminal Settings screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 40 Before configuring the Ethernet print settings, make sure that the print server is available on the PC. To do so, the printer driver must be installed on the PC and the printer must be shared on the network. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 41 IMPORTANT If your account does not have a password, leave the Password field blank. If your PC is not part of a domain or workgroup, enter the name of your PC in the Domain field. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 42: System Information Settings

    Boot Code Version: 4.011 Logic Board Version: Terminal On Time: 102,330 Display On Time: 102,330 Battery Status: Good Memory Usage (bytes) Internal Used: 1,392,640 Internal Free: 164,741,120 Advanced Application Used: 31,600,640 Main Application Free: 193,994,752 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 43: View System Information

    PanelView 800 terminals. For example, you might create an application for one terminal and then distribute the application to other terminals for production. An application that is created for PanelView 800 terminals cannot be used on older PanelView Component terminals. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 44 (for example, an Ethernet application on a terminal without an Ethernet network connection). PanelView 800 applications are saved with a “.cha” file type. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 45: Designstation In Connected Components Workbench Software

    Applications that are designed for CompactLogix 5370™ or CompactLogix 5380 controllers must be validated before running on the terminal. You can download the latest version of Connected Components Workbench software at rok.auto/ccw. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 46: Install The Software

    Connected Components Workbench software version 11 is used in the following examples. 1. Run the executable file. (a) Requires Connected Components Workbench software version 20 or earlier. (b) Requires Connected Components Workbench software version 20 or later. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 47 “Customize” to select the individual components to install. 3. If you chose “Customize”, select the components that you want to install, then click Install. Certain components are pre- selected for you and cannot be unchecked. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 48 Chapter 3 DesignStation in Connected Components Workbench Software 4. Review the license agreement and click Accept all to proceed with the installation. 5. The next screen provides a visual indication of the installation progress. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 49: Uninstall The Software

    Windows Start menu items that were originally installed with this software. Follow these steps to uninstall Connected Components Workbench software. 1. Run the same executable file used to install Connected Components Workbench software. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 50 Controller - Micro800 3. After you have unselected the checkboxes of the components that are listed above, you can then unselect the checkbox for Connected Components Workbench software. Click Install to proceed with the uninstallation. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 51 DesignStation in Connected Components Workbench Software 4. The next screen provides a visual indication of the uninstallation progress. 5. When the uninstallation is successfully completed, a final confirmation screen is shown. Click Close to end the uninstallation process. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 52: Launch Mechanism

    Follow these steps to change the repeat settings for keys using Connected Components Workbench software. 1. Go to the Settings tab for your PanelView 800 terminal. 2. Click Advanced in the settings list. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 53: Creating Applications

    Connected Components Workbench software version 9 or earlier. An error message stating the system is busy will be shown in the output window under the Graphic Terminal message list. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 54: Uploading Applications

    Alternatively, click the Upload icon in the Settings tab of the terminal. The Connection Browser dialog box appears. 2. Select the terminal that you want to upload the application from, then click OK. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 55: Create Recipes

    If non-English characters are used, the field is outlined in red and the OK button is dimmed. 4. You can optionally assign a Status Tag to monitor the status of the recipe downloads and uploads. You can now add ingredients to the recipe. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 56: Add Ingredients To A Recipe

    3. Click Yes to confirm. Download Recipes Recipes are downloaded together with the application into the PanelView 800 terminal. See Downloading Applications on page 53 for information on how to download applications to the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 57: Configure Ftp Settings

    None of the checkboxes are selected by default. To connect to the terminal, enter the IP address of the terminal in the FTP client. For this example, the PC file explorer is used. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 58: Configure Email Settings

    IMPORTANT The Email feature is not available for CompactLogix 5370 and CompactLogix 5380 controllers. Configure the Email settings Follow these steps to configure the email settings. 1. In the Connected Components Workbench software, click on the Settings tab for your PanelView 800 terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 59 • Email Address = The “From” or “Sender” email address that is associated with the account when sending an email. 5. Under the Recipients Settings configuration, enter the email addresses of the recipients in the “To”, “Cc”, and “Bcc” fields as required. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 60 • $SysEmailSTARTTLS = 1 – Enable email STARTTLS encryption, 0 – Disable email STARTTLS encryption. • $SystEmailTLS = 1 – Enable email TLS encryption, 0 – Disable email TLS encryption. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 61: Configure The Alarm Settings

    • Send Email = Select this checkbox to enable the terminal to send an email when the alarm is triggered. • Subject = This field is sent as the subject of the email. You can configure the subject with Date, Time, Number, and String variables. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 62: Change Application Font

    2. Select the font to use from the Font pull-down list. To import a font, select Import Font. 3. Browse your computer for the font, then select it and click Open. The font is now imported into your application. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 63: Add Fonts To The Terminal

    If your application uses a font that is not in the terminal, the font is download to the terminal together with your application. Follow these steps to download a font to the terminal. 1. In Connected Components Workbench software, click Device -> Download -> Download Font. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 64: Add Screen Savers To The Terminal

    You can change the screen saver by downloading them to the terminal. The terminal supports up to 25 screen savers and the screen saver has the following requirements: • Maximum resolution of 128 x 128 pixels. • In bitmap (.bmp) file format. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 65: Trend And Datalog

    Follow these steps to add a Trend object to your PanelView 800 application. 1. In Connected Components Workbench software, double-click an application screen to open it. 2. Drag-and-drop a Trend object from the Toolbox onto the screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 66 True = The trend always updates. • Log File Location: Select the location where the datalog file is saved. • Log Trigger Tag: The datalog starts recording when the value of the tag is TRUE. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 67: Alarm List Filter

    Tag Selector dialog. However, if the tag contains sub tags that have supported data types, then the main tag and sub tags are shown in the Tag Selector dialog. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 68: Import Tags From A Compactlogix Controller

    PanelView 800 application. For more information on the differences in supported data types between PanelView 800 terminals and CompactLogix 5370/CompactLogix 5380 controllers, see CompactLogix 5370 and CompactLogix 5380 Controller Addressing on page 141. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 69: Import Tags From A Micro800 Controller

    Follow these steps to configure the controller tags and assign them to your PanelView 800 terminal tags. 1. Under Communication settings in the Settings tab, click the ellipses (...) button for Offline File Path. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 70: Export And Import A Language List

    If you selected an existing file, a warning message appears. Click Yes to overwrite the existing file or No to cancel the action. The Export Language List results are shown in the Output pane. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 71: Import A Language List

    You can import text information for a language that has not been set on the terminal. Make sure that the column header contains a Language ID and it will be imported to Languages on the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 72: Update Tag Name

    Animation With Tag • If Animation With State is selected, the following tags are not configurable: • Height Tag • Horizontal Position Tag • Vertical Position Tag • Visibility Tag • Width Tag Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 73 Retains most recent value when application is shut down Initial Value Defines the coordinates of the starting position Description Enters a description for the Memory tag Data Entry - Min -32768 Data Entry - Max -32767 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 74: Time Entry Data Type Support

    Time data type for Micro800 controllers. From the Object Properties, click Format, set the attribute Time Datatype Entry to True. When changing the time in the application, the value is displayed in the onscreen keyboard. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 75: View List Of Objects

    • Allen-Bradley Micro800 CIP Serial Communication • Allen-Bradley CompactLogix CIP Communication • Allen-Bradley MicroLogix CIP Communication • DF1 Serial Communication • Modbus Ethernet Communication • Modbus RTU Communication • Modbus RTU Unsolicited Communication Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 76: Allen-Bradley Micro800 Cip Ethernet Communication

    Specify the number of times the terminal repeats the Fail After communication request before the request is considered 1…10 a failed attempt, and the controller is in error. PanelView 800 Settings No configurable parameters are available for this communication protocol. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 77: Allen-Bradley Micro800 Cip Serial Communication

    (cannot be changed) Data Bits The number of data bits per data word. (cannot be changed) Station Address Specify the node address of the terminal on the network. 0…255 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 78: Allen-Bradley Compactlogix Cip Communication

    Inter Request Delay Specify how long the terminal waits before sending 0…300000 Milliseconds another request to the controller. PanelView 800 Settings No configurable parameters are available for this communication protocol. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 79: Allen-Bradley Micrologix Cip Communication

    Inter Request Delay Specify how long the terminal waits before sending 0…300000 Milliseconds another request to the controller. PanelView 800 Settings No configurable parameters are available for this communication protocol. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 80: Df1 Serial Communication

    (cannot be changed) Data Bits The number of data bits per data word. (cannot be changed) Station Address Specify the node address of the terminal on the network. 0…255 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 81: Modbus Ethernet Communication

    Sets the block size of the input coils. (in multiples of 8) Internal Registers Sets the block size of the internal registers. 1…120 Holding Registers Sets the block size of the holding registers. 1…120 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 82: Modbus Rtu Communication

    Specify the port number that the remote device is 0…65535 Port configured to use. Default is 2101 Only applicable when Ethernet Encapsulation is enabled. The type of Ethernet protocol. TCP/IP Protocol Only applicable when Ethernet Encapsulation is enabled. (cannot be changed) Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 83 Sets the block size of the input coils. (in multiples of 8) Internal Registers Sets the block size of the internal registers. 1…120 Holding Registers Sets the block size of the holding registers. 1…120 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 84: Modbus Rtu Unsolicited Communication

    Modify this setting carefully. Stop Bits Specify the number of stop bits per data word. 1…2 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 85 Modify this setting carefully. TCP/IP Protocol The type of Ethernet protocol. (cannot be changed) Address Specify the node address of the terminal on the network. All values Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 86 Chapter 3 DesignStation in Connected Components Workbench Software Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 87: Secure The Terminal

    2. Enter the new password in the Password and Confirm Password fields. Use the following guidelines when creating a password: • Passwords must be 8...32 characters in length. • Valid characters are uppercase and lowercase letters, numbers, symbols found on the keyboard and spaces. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 88: Change Terminal Password

    Use the following guidelines when creating a password: • Passwords must be 8...32 characters in length. • Valid characters are uppercase and lowercase letters, numbers, symbols found on the keyboard and spaces. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 89: Clear Terminal Password

    Protect the application from updates by restricting user access to design mode. Only users with design rights are allowed to access and update an application. Initially, all users have design rights to an application. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 90: Manage User Accounts Settings

    Follow these steps to access the User Accounts screen. Settings 1. In the main screen of Connected Components Workbench software, click the Settings tab for your PanelView 800 terminal. 2. Click User Accounts in the options list. User Accounts Screen Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 91: Add Users

    Follow these steps to add user accounts to the application. 1. Select the Design Environment Secured checkbox. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 92: Managing Users

    To select multiple rows, hold down the CTRL or SHIFT key and click the desired rows. If you delete all users, then you are left with All Users* which gives any user unrestricted access to the application. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 93: Assign Design Rights

    For example, you can assign maintenance rights to users that need to access the maintenance screens at runtime. IMPORTANT We recommend that you do NOT assign any rights to the Startup screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 94: Managing Rights

    To delete a right, click the column header to select it and click the Delete Right(s) button. Any assignments of that right to users are also deleted. To rename a right, click the column header ellipses button and type a new name. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 95: Assign Rights To A Screen

    User Accounts screen in the Settings tab. Changing Terminal Settings To prevent unauthorized changing of terminal settings at runtime, such as network configuration or the startup application, assign an access right to screens that contain the Goto Config button. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 96: Security At Runtime

    Displays the startup screen whether the last displayed screen was secured or unsecured. • Enables security if it was previously disabled. • Retains changed passwords. • The current user tag and current user rights tag is cleared when the terminal resets. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 97: Starting The Terminal In Safe Mode

    After the boot-up process and the terminal displays a terminal configuration screen. After the boot-up process and the terminal loads a startup application. An application is loaded. An application is unloaded successfully and the terminal displays a terminal configuration screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 98 Internal Internal Delete PV800_App1 Set As Startup PVcApplication1 Stop Application Recipe Copy Alarm History Controller Settings Startup Application Reset Main IMPORTANT The Stop Application button is only available in firmware revision 3.011 onwards. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 99: Virtual Network Computing

    These are the recommended VNC clients for use with PanelView 800 terminals. Recommended VNC Clients and Settings Client Name Remote Connection Type Recommended Settings Change Preferred Encoding from “Tight” to “Hextile” for Tight VNC PC/Laptop – Windows 7 smoother screen switching. Rockwell Automation Publication 2711R-UM001I-EN-E - April 2022...
  • Page 100: Configure Vnc Settings

    English Português Terminal Setting Français Italiano Month Minute Deutsch Español 简体中文 Year Second System Information Reset Terminal 2015 2. Press Terminal Setting. Terminal Setting Communication Display Error Alert Display Settings Print Settings Main Rockwell Automation Publication 2711R-UM001I-EN-E - April 2022...
  • Page 101 (2) Once a password is set, you can only change it. You cannot clear a password unless you perform a restore operation or return the terminal to the out-of-box condition. See Returning to the Out-of-box Condition on page 113 Restoring the Terminal on page 114 for instructions. Rockwell Automation Publication 2711R-UM001I-EN-E - April 2022...
  • Page 102: Set The Password For Vnc Connection

    Status: Esc F1 F9 F10 F11 F12 Home End Server: Enable / Disable Server: Enabled Access: View-Only / Control Access: View-Only ’ Caps View-Only: Control: Shift Reset Password Reset Password Ctrl Win Back Rockwell Automation Publication 2711R-UM001I-EN-E - April 2022...
  • Page 103: Establish Vnc Connection To The Terminal

    A window opens on your desktop showing the current screen on the terminal. 4. To terminate the VNC connection to the terminal, simply close the VNC. Viewer application. Rockwell Automation Publication 2711R-UM001I-EN-E - April 2022...
  • Page 104 Chapter 5 Virtual Network Computing Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - April 2022...
  • Page 105: Troubleshoot The System

    Follow these steps to view the system information on your terminal. 1. Go to the PanelView Explorer Startup window. 2. Click the Terminal Settings link. 3. Click the System Information tab. 4. View the information. 5. Click Apply. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 106: Alerts

    Set this external tag as write and remove panel devices from your application that can read data from this external tag. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 107 Add a Recipe Table Panel device to the Screen. Recipe /*S:0 Param1*/ operation was not started because the Wait for a recipe operation to complete before starting the next Recipe 1018 system is currently busy performing another Recipe operation. recipe operation. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 108 Insufficient space to complete file copy. Remove files to free space from the destination and try again. Alert 2022 Source and destination cannot be the same. Verify that the source and destination are not the same and retry. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 109 Screen navigation devices are disabled if the screen has been Alert 2053 Screen switching controlled by external source. changed to via controller. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 110 Make sure that the View-Only password does not contain any Alert 2080 special character. special characters. Make sure that the correct password is entered in the Old Alert 2081 Old password does not match with terminal. Password field. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 111: Troubleshooting

    Determine what changed since the last time the terminal ran normally and decide if the change can be reversed. Check for Adequate Power A terminal that does not receive adequate power could cause unpredictable behavior. Verify the power requirements in the Specifications table. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 112: Observe Splash Screen

    Application Load and Execute Load N4…N6 POST errors are fatal and most likely due to failed hardware. A fatal error during firmware installation and loading is most likely recoverable by installing the appropriate firmware. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 113: Interpret The Led Indicators At Startup

    Restart the terminal and wait until the boot screen displays the INIT code N1, then press and hold the Ctrl and Shift keys until the dialog box appears. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 114: Restoring The Terminal

    Settings Cleared or Reset to Default When Using Restore or in Out-of-Box Condition Setting Restore Out-of-Box Condition Applications Terminal Startup Application User-Installed Font Files Screensaver VNC Settings Port Settings FTP Settings Print Settings Network Credentials Terminal Password DHCP Option IP Address Subnet Mask Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 115 ©2016 Rockwell Automation, Inc. All Rights Reserved. BOOT 4. Wait for a few minutes until the process is completed. 5. When the restore process is completed, the terminal boots into the main configuration screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 116 Chapter 6 Troubleshoot the System Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 117: Update Firmware

    The VNC feature is only supported on PanelView 800 terminals with firmware revisions 4.011…7.011. For more information, contact your local technical support at rok.auto/phonesupport. 1. Backup applications and library objects from the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 118 If you have not saved changes to the application, you are prompted to do so. Once the application is unloaded, the terminal displays the Configuration screen. 3. Close the web browser that is connected to the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 119: Upgrading Firmware Using Controlflash

    See the details in step 4 for more information. Follow these steps to upgrade the firmware using ControlFLASH. 1. Verify that the terminal is connected to your computer either through Ethernet or USB. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 120 The Firmware Kit Locations dialog box appears. b. Click Add. c. Select the folder that contains the firmware DMK file, and then click OK. d. Click OK to close the Firmware Kit Locations window. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 121 Appendix A Update Firmware 5. Select the terminal in the connection browser window and click OK. 6. Select the firmware revision to update and click Next. 7. Verify your selections and click Finish. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 122 Memory Usage (bytes) Internal Used: 1,392,640 Internal Free: 164,741,120 Advanced Application Used: 31,600,640 Main Application Free: 193,994,752 View System Information on page 43 for instructions on how to view the current firmware revision. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 123: Firmware Installation Using Removable Storage Device

    Be aware of the firmware revision for the terminal versus the new firmware that is on the computer, and be informed of the expected behavior after the new firmware is installed on the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 124: Extract The Rfu Files From The Dmk File

    • Do not remove the microSD card or USB drive during the firmware update. Wait until the process is complete and the message, “upgrade — OK” is show on the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 125 Memory Usage (bytes) Internal Used: 1,392,640 Internal Free: 164,741,120 Advanced Application Used: 31,600,640 Main Application Free: 193,994,752 View System Information on page 43 for instructions on how to view the current firmware revision. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 126 Appendix A Update Firmware Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 127: Chapter Objectives

    • USB drive • Battery replacement microSD Memory Card The microSD memory card can be inserted in the following locations on the PanelView 800 terminals. 2711R-T4T 2711R-T7T 2711R-T10T microSD memory card slot Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 128: Usb Drive

    For Safety information on the handling of lithium batteries, including handling and disposal of leaking batteries, see Guidelines for Handling Lithium Batteries, publication AG-5.4. Do not dispose of battery in a fire or incinerator. Dispose of used batteries in accordance with local regulations. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 129 This equipment is sensitive to electrostatic discharge (ESD). Follow ESD prevention guidelines when handling this equipment. Battery Battery cover This equipment is sensitive to electrostatic discharge (ESD). Follow ESD prevention guidelines when handling this equipment. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 130 Appendix B Install and Replace Components Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 131: Chapter Objectives

    Grounding minimizes noise from EMI and is a safety measure in electrical installation. For more information on grounding recommendations, see the National Electrical Code that is published by the National Fire Protection Association. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 132: Connecting Devices

    Ethernet (AB CIP) Ethernet 2711P-CBL-EX04 (CAT5 Ethernet) — 2711P-CBL-EX04 (CAT5 Ethernet) Serial (AB CIP) RS-232 1761-CBL-PM02 1761-CBL-PM02 – (1) Terminal block, wiring required. (2) RS-485 is isolated. We recommend that you connect only one device. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 133: Compactlogix 5370 And Compactlogix 5380 Controller Cable Charts

    Connected Components Workbench software to the terminal. Ethernet Connector The base-configured unit of the terminals has an RJ45, 10/100 Base-T connector for Ethernet network communication. 2711R-T4T 2711R-T7T 2711R-T10T Ethernet port Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 134: Cables

    SNMP (Simple Network Management Protocol) is used for internal network management and is not supported. Ports 137 and 138 are normally open to support the NetBIOS protocol that is used by Windows CE.NET similar to other Microsoft® and IBM network operating systems. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 135: Serial Connections

    The RS422/485 port has integrated 120 ohm termination between the R and R- signal pair. This value is compatible with RS422 and RS-485 electrical specifications. Additional termination on the PanelView 800 terminal end of communication cables is not required. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 136: Usb Ports

    USB drive or microSD card from being accidentally disconnected. Also, do not power off the terminal while a firmware update is in progress. USB hubs can produce unexpected behaviors and as a result are not recommended. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 137: Add A Compactlogix 5370 Or Compactlogix 5380 Controller

    CompactLogix 5380 application, do the following: Controller 1. Click on the Settings tab for your PanelView 800 terminal in Connected Components Workbench software. 2. Click the Communication item in the menu list. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 138: Map The Terminal And Controller Tags

    Map the Terminal and Here is an example of the terminal screen that we will use to map the Controller Tags PanelView 800 terminal tags to the CompactLogix 5370 or CompactLogix 5380 controller tags. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 139: Validate The Application

    CompactLogix 5380 controller tag in PanelView 800, see Addressing Formats from PanelView 800 Terminals to CompactLogix 5370 or CompactLogix 5380 Controllers on page 142. Validate the Application Before you can download the application to the terminal, you must validate it. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 140: Download The Application

    1. Click the Download icon in the Settings tab of the terminal. The Connection Browser dialog box appears. 2. Select the terminal that you want to download the application to, then click OK. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 141: Upload The Application

    If a structure member is a structure itself, both structures would have to be expanded to access an atomic member of the substructure. This is more common with user-defined and module-defined types and is not found in any of the predefined types. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 142: Addressing Formats From Panelview 800 Terminals To Compactlogix 5370 Or Compactlogix 5380 Controllers

    Tag3.bitNo Boolean SINT Program:MainProgram.Tag4.bitNo Tag4.bitNo (1) bitNo can be any value – 0...31 for DINT, 0...15 for INT and 0...7 for SINT data type tags in the CompactLogix 5370 or CompactLogix 5380 controller. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 143: Support

    • The following CompactLogix 5380 controllers are supported in PanelView 800 terminals with firmware revision 6.012 or later: - 5069-L306ER, 5069-L306ERM, 5069-L306ERS2, 5069-L406ERMS2, and 5069-L306ERMS3 • FTP and Email features are not supported. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 144 Appendix D Using PanelView 800 Terminals with CompactLogix 5370 and CompactLogix 5380 Controllers Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 145: Chapter Objectives

    The browser interface requires a computer browser that is connected to the terminal's web service through an Ethernet network connection. The configuration data for a terminal refers to the collection of all system interface parameters. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 146: Configure Using The Browser

    The recommended browsers to use are: • Internet Explorer 7 or 8 • Firefox 3.0 If you use a browser other than a recommended browser, you may encounter messages similar to the following examples. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 147: Terminal Settings

    Adjusting Settings on the PanelView Explorer Startup Window From the PanelView Explorer Startup window, you can view and edit settings for the connected PanelView 800 terminal. The settings take effect immediately. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 148: Select A Terminal Language

    At runtime, diagnostic messages appear in the same language as the IMPORTANT application if the application language is English, Portuguese, French, Italian, German, Spanish, Chinese, or Korean. For all other languages, the diagnostic messages appear in the configuration language set on the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 149: Adjust The Display Brightness

    2. Click the Terminal Settings link. 3. Click the Display/Input tab. 4. Drag the slider to adjust the brightness level between 1…100%. 5. Click Apply, or click Cancel to restore the current terminal settings. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 150: Configure The Screen Saver

    6. Drag the slider to adjust the screen saver brightness. 7. Click Apply, or click Cancel to restore the current screen saver settings. To disable the screen saver or dimmers, select Disable Screen Saver and Dimmer from the screen saver mode list. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 151: Replace The Screen Saver Image

    The new screen saver takes effect the next time the screen saver is activated. Your bitmap file should be small in size. A large bitmap will impact performance of terminal operations. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 152: Configure Key Repeat Settings

    Over time you may notice that the objects and images on the display screen don’t seem to fit the display area as well as they once did. This is normal with a touch screen and can be easily fixed. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 153 3. Click the Display/Input tab. 4. Click Calibrate Touch Screen. Follow these steps to complete the calibrate touch screen procedure. 1. With a stylus, tap the center of the target (+) on the terminal screen. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 154: Restart The Terminal

    Follow these steps to restart the terminal from PanelView Explorer. 1. Go to the PanelView Explorer Startup window. 2. Click the Terminal Settings link. 3. Click the Display/Input tab. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 155: Change The Startup Application

    1. Go to the PanelView Explorer Startup window. 2. Click the Terminal Settings link. 3. Click the System Information tab. 4. Select the name of the startup application from the Startup Application pull-down list. 5. Click Apply. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 156: Change The Date And Time

    Initially, the terminal and the PanelView Explorer Startup window are unsecured. To enable security, provide a password. The default user name is Admin. The new password takes effect the next time the terminal is restarted. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 157 8. Select a new idle timeout from the Terminal Idle Timeout list, if needed, or click Cancel to restore the current idle timeout. The new password and idle timeout value take effect when the terminal is restarted. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 158: View System Information

    You can do the following actions: • Export or import applications, images, the terminal security file, recipes, and fonts. • Import screen saver bitmap files. • Export the alarm log from the currently running application. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 159: Adding Font Files

    Windows CE licensed fonts can be added to the terminal. Windows CE licensed fonts can be downloaded from the PanelView 800 technical support website at rok.auto/pv800. No other fonts are licensed for use on the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 160: Import A Font File

    Observe the list of all Font files that have been added to the Terminal. 6. Select the Font file that you want to delete and click Delete. 7. Observe the Confirmation message for the selected Font file and click 8. Observe the informational message Deleting File. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 161 10. Restart the terminal to remove the file from the terminal. Font files, especially East Asian Fonts, are large and consume significant space on Internal Storage. Remove all unused fonts from the terminal. Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 162 Appendix E PanelView Explorer Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 163: Index

    22 import font 160 Connected Components Workbench software install download 45 battery 128 installation requirements 46 SD memory card 127 launch mechanism 52 USB flash drive 128 uninstallation 49 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 164 39 PVc DesignStation in Connected Components restore 114 Workbench 87 return to out-of-box condition 113 set password 87 system information 43 terminal interface main menu 18 reboot terminal 20 PanelView explorer window 154 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 165 Virtual Network Computing (VNC) troubleshooting 111 connecting 103 alerts 106 guidelines 99 check for power 111 settings 101 out-of-box condition 113 VNC clients 99 restore the terminal 114 status indicators 113 wiring and safety guidelines 131 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 166 Index Notes: Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 167 PanelView 800 HMI Terminals User Manual Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023...
  • Page 168 Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Connect with us. ASIA PACIFIC: Rockwell Automation SEA Pte Ltd., 2 Corporation Road, #04-05, Main Lobby, Corporation Place, Singapore 618494, Tel: (65) 6510-6608, Fax: (65) 6510-6699 Publication 2711R-UM001I-EN-E - February 2023 Supersedes Publication 2711R-UM001H-EN-E - April 2021 Copyright ©...