Rockwell Automation PanelView Plus Series Installation Instructions Manual

Rockwell Automation PanelView Plus Series Installation Instructions Manual

Terminals and display modules
Hide thumbs Also See for PanelView Plus Series:

Advertisement

PanelView Plus 700 to 1500 and PanelView Plus
Compact 1000 Terminals and Display Modules
Catalog Numbers 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx,
2711PC-T10C4D1
Topic
About This Publication
This document provides instructions on how to install these devices in a panel.
• Factory-assembled PanelView Plus or PanelView Plus CE 700 to 1500 terminals
• PanelView Plus or PanelView Plus CE 700 to 1500 display modules
• Factory-assembled PanelView Plus Compact 1000 terminal
For complete information on installing, wiring, and troubleshooting the terminals, refer to the
publications listed under Additional Resources.
Installation Instructions
Page
2
3
4
8
8
10
10
10
16
20
22
24
28
30

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation PanelView Plus Series

  • Page 1: Table Of Contents

    Installation Instructions PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Catalog Numbers 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-T10C4D1 Topic Page Important User Information Environment and Enclosure Hazardous Locations Wiring and Safety Guidelines About the PanelView Plus 700 to 1500 Terminals Parts List Required Tools Install the Terminal...
  • Page 2: Important User Information

    In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
  • Page 3: Environment And Enclosure

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in ATTENTION overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
  • Page 4: Hazardous Locations

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Hazardous Locations This equipment is suitable for these locations: • Class I, Division 2 Groups A, B, C, D • Class II, Division 2 Groups F, G •...
  • Page 5 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Environnements dangereux Cet équipement ne peut être utilisé que dans les environnements suivants : • Classe I, Division 2, Groupes A, B, C, D • Classe II, Division 2, Groupes F, G •...
  • Page 6 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules USB Ports All PanelView Plus and PanelView Plus Compact terminals contain universal serial bus (USB) ports that comply with hazardous location environments. This section details the field-wiring compliance requirements and is provided in accordance with the National Electrical Code, article 500.
  • Page 7 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Application Information Per the National Electrical Code the circuit parameters of nonincendive field wiring apparatus for use in hazardous locations shall be coordinated with the associated nonincendive field wiring apparatus such that their combination remains nonincendive.
  • Page 8: Wiring And Safety Guidelines

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Wiring and Safety Guidelines Use publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces, IEC 60364 Electrical Installations in Buildings, or other applicable wiring safety requirements for the country of installation when wiring the devices.
  • Page 9 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Modular Components Communication Module Power Input, AC or DC Logic Module Display Module Ethernet Port Serial Port USB Ports CompactFlash Card Slot If the modules are ordered separately, attach the logic and communication module to the display module before panel installation.
  • Page 10: Parts List

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Parts List These items are shipped with the terminals: • Power terminal block • Mounting clips • FactoryTalk View software preloaded • Installation instructions and panel cutout template Required Tools These tools are required for panel installation: •...
  • Page 11 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Panel Cutout Dimensions Use the full size template shipped with your terminal to mark the cutout dimensions. Terminal Type Height, mm (in.) Width, mm (in.) 700 Keypad or Keypad and Touch 167 (6.57) 264 (10.39) 700 Touch...
  • Page 12 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules This gasket forms a compression type seal. Do not use sealing compounds. Sealing Gasket 3. Install the legend strips before installing the terminal if you are using keypad legend strips on keypad terminals.
  • Page 13 Tighten the mounting clips to the specified torque to provide a proper seal and prevent ATTENTION damage to the product. Rockwell Automation assumes no responsibility for water or chemical damage to the product or other equipment within the enclosure because of improper installation.
  • Page 14 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules The illustration shows product dimensions for the PanelView Plus and PanelView Plus Compact 1000 touch only terminals. The other size terminals look similar. Measurements are in mm (in.). 1000 Terminal Dimensions Keypad or Keypad &...
  • Page 15 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Ethernet Wiring Use Belden 7921A shielded Ethernet Category 5e cable according to TIA 568-B.1 and RJ45 connector according to IEC 60603-7 for compliance with Marine emissions limits and European Union 89/336/EEC EMC Directive.
  • Page 16: Dc Power Connections

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Follow these steps to remove the terminal block. 1. Loosen the two screws that secure the terminal block. 2. Gently pull the terminal block away from the connector. 3-position AC or DC 2-position DC Terminal Block Terminal Block...
  • Page 17 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules External Power Supply For Non-isolated DC Terminals To identify non-isolated DC logic modules refer to the PanelView Plus Terminals user manual, publication 2711P-UM001. Use a single, 24V DC power supply to power each PanelView Plus device, such as catalog number 2711P-RSACDIN.
  • Page 18 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules External Power for Isolated DC Terminals Isolated DC logic modules are identified by catalog number 2711P-RPxDx. Use an SELV or PELV 24V DC power supply, such as catalog number 2711P-RSACDIN, to power the isolated DC PanelView Plus terminal.
  • Page 19 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Connect DC Power Explosion Hazard - Do not disconnect equipment unless power has been switched off and WARNING area is known to be nonhazardous. Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock or damage to the terminal.
  • Page 20: Ac Power Connections

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules AC Power Connections PanelView Plus devices with an integrated AC power supply have these power ratings: • 85…264V AC (47…63 Hz) • 160V A max The input power terminal block supports these wire sizes. Wire Specifications for AC Input Power Terminal Block Dual-wire Single-wire...
  • Page 21 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Connect AC Power Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless WARNING area is known to be nonhazardous. Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock and/or damage to the terminal.
  • Page 22: Battery Precautions

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Battery Precautions When you connect or disconnect the battery an electrical arc can occur. This could cause WARNING an explosion in hazardous location installations. Be sure that power is removed and the area is nonhazardous before proceeding.
  • Page 23 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 6. Locate the battery on the circuit board. Lift up the edge of the battery indicated by the arrow. 7. Remove the battery by lifting up the side of the battery. 8.
  • Page 24: Troubleshooting

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 12. Reattach the communication module, if necessary, and tighten the four screws to a torque of 0.58 N•m (5…7 lb•in). This product contains a hermetically sealed lithium battery which may need to be replaced during the life of the product.
  • Page 25 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules The table shows indicator states if the terminal powers on and stops during startup. Indicator States If the Terminal Stops During Startup Fault (Red) Comm (Green) Description Indicator Indicator...
  • Page 26 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Startup Information Messages Startup information messages display in a specific sequence on the terminal during startup and typically display for a few seconds. These messages do not require that you perform any action.
  • Page 27 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Startup Error Messages When an error occurs, the terminal displays an error number with a text message. The word ERROR! appears under the message in different languages. # Displayed Message ERROR! FEHLER! ERREUR! ERRORE! Error #...
  • Page 28: Specifications

    PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Specifications PanelView Plus Terminals - 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-Txxxx Attribute Value Display Display type Color active matrix, thin film transistor (TFT), liquid crystal display (LCD) Display size 6.5 in.
  • Page 29 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules PanelView Plus Terminals - 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-Txxxx Weight, Approx. for base configured unit without communication module 700 keypad, or keypad and touch 1.9 kg (4.2 lb) 700 touch 1.7 kg (3.8 lb) 1000 keypad, or keypad and touch...
  • Page 30: Additional Resources

    You can view or download publications and translated versions of the installation instructions at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative. Publication 2711P-IN001I-EN-P - November 2009...
  • Page 31 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Publication 2711P-IN001I-EN-P - November 2009...
  • Page 32 New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

This manual is also suitable for:

Panelview plus 700Panelview plus 1000Panelview plus 1250Panelview plus 1500Panelview plus compact 10002711pc-t10c4d1

Table of Contents