Operation; Control Panel; Start-Up Guide - Grundfos CUE Series Product Manual

Frequency converters for pump control 60 hz
Table of Contents

Advertisement

Operation

Control panel

The control panel is used for local setting of the CUE.
The functions available depend on the pump family.
On/
On/
Off
OK
On
On
Off
Alarm
Alarm
Fig. 47 Control panel of the CUE
Editing buttons
Button
Function
Makes the pump ready for operation/starts and stops
On/
On/
the pump.
Off
Saves changed values, resets alarms and expands the
OK
value field.
-
+
Changes values in the value field.
Navigating buttons
Button
Function
Navigates from one menu to another. When the menu
>
is changed, the display shown will always be the top
display of the new menu.
Navigates up and down in the individual menu.
Indicator lights
The operating condition of the pump is indicated by the
indicator lights on the front of the control panel. See fig.
47.
The table shows the function of the indicator lights.
Indicator light
Function
The pump is running or has been stopped by a stop
function.
On (green)
If flashing, the pump has been stopped by the user
(CUE menu), external start/stop or bus.
Off (orange)
The pump has been stopped with the on/off button.
Alarm (red)
Indicates an alarm or a warning.
CUE
CU
+
-
>

Start-up guide

Use the start-up guide for the general setting of the
CUE including the setting of the correct direction of
rotation.
The start-up guide is started the first time when the
CUE is connected to supply voltage. It can be restarted
in menu GENERAL. Please note that in this case all
previous settings will be erased.
Grundfos CUE
37

Hide quick links: