Grundfos CUE Series Product Manual page 33

Frequency converters for pump control 60 hz
Table of Contents

Advertisement

Installation
Mains and motor connection
The supply voltage and frequency are marked on the
CUE nameplate. Make sure that the CUE is suitable for
the electricity supply of the installation site.
Mains switch
A mains switch can be installed before the CUE accord-
ing to local regulations. See fig. 38.
Wiring diagram
The wires in the terminal box must be as short as pos-
sible. Excepted from this is the protective conductor
which must be so long that it is the last one to be dis-
connected in case the cable is inadvertently pulled out
of the cable entry.
Fig. 39 Wiring diagram, three-phase mains connection
Terminal
Function
91
(L1)
92
(L2)
Three-phase supply
93
(L3)
95/99
(PE)
Earth connection
96
(U)
Three-phase motor connection, 0-100 % of mains
97
(V)
voltage
98
(W)
Note: use terminals 91 and 92 for single phase CUE's.
Connecting the signal terminals
Note: As a precaution, signal cables must be separated
from other groups by reinforced insulation in their entire
lengths.
Note: If no external on/off switch is connected, short-
circuit terminals 18 and 20 using a short wire.
Wiring diagram, signal terminals
0/4-20 mA
0-10 V, 4-20 mA
1 K
Fig. 40 Wiring diagram, signal terminals
Terminal
Type
Function
12
+24 V out
Supply to sensor
13
+24 V out
Additional supply
18
DI 1
Digital input, start/stop
19
DI 2
Digital input, programmable
20
GND
Common frame for digital inputs
32
DI 3
Digital input, programmable
33
DI 4
Digital input, programmable
39
GND
Frame for analog output
42
AO 1
Analog output, 0-20 mA
50
+10 V out
Supply to potentiometer
53
AI 1
External setpoint, 0-10 V, 0/4-20 mA
54
AI 2
Sensor input, sensor 1, 0/4-20 mA
55
GND
Common frame for analog inputs
61
RS-485 GND Y GENIbus, screen (frame)
68
RS-485 A
GENIbus, signal A (+)
69
RS-485 B
GENIbus, signal B (-)
Terminals 27 and 29 are not used.
Connect the signal cables according to the guidelines
for good practice to ensure EMC-correct installation.
See section EMC-correct installation, 35.
• Use shielded signal cables.
• Use a 3-conductor shielded bus cable.
Grundfos CUE
4-20 mA
Terminals
53 and 54:
U = 0-10 V
I = 4-20mA
33