Menu Operation - Grundfos CUE Series Installation And Operating Instructions Manual

Table of Contents

Advertisement

10.4.3 Copy of settings
It is possible to copy the settings of a CUE and reuse them in
another one. Options:
No copy.
to CUE (copies the settings of the CUE).
to control panel (copies the settings to another CUE).
The CUE units must have the same firmware version. See section
10.6.16 Firmware version (2.16).

10.5 Menu OPERATION

10.5.1 Setpoint (1.1)
Setpoint set
Actual setpoint
Actual value
Set the setpoint in units of the feedback sensor.
In control mode Open loop, the setpoint is set in % of the
maximum performance. The setting range will lie between the
min. and max. curves. See fig. 44.
In all other control modes except proportional differential
pressure, the setting range is equal to the sensor measuring
range. See fig. 45.
In control mode Proportional differential pressure, the setting
range is equal to 25 % to 90 % of max. head. See fig. 46.
If the pump is connected to an external setpoint signal, the value
in this display will be the maximum value of the external setpoint
signal. See section 13.2 External setpoint.
10.5.2 Operating mode (1.2)
Set one of the following operating modes:
Normal (duty)
Stop
Min.
Max.
The operating modes can be set without changing the setpoint
setting.
10.5.3 Fault indications
Faults may result in two types of indication: Alarm or warning.
An "alarm" will activate an alarm indication in CUE and cause
the pump to change operating mode, typically to stop. However,
for some faults resulting in alarm, the pump is set to continue
operating even if there is an alarm.
A "warning" will activate a warning indication in CUE, but the
pump will not change operating or control mode.
Alarm (1.3)
In case of an alarm, the cause will appear in the display.
See section 15.1 Warning and alarm list.
Warning (1.4)
In case of warning, the cause will appear in the display.
See section 15.1 Warning and alarm list.
10.5.4 Fault log
For both fault types, alarm and warning, the CUE has a log
function.
Alarm log (1.5-1.9)
In case of an "alarm", the last five alarm indications will appear in
the alarm log. "Alarm log 1" shows the latest alarm, "Alarm log 2"
shows the latest alarm but one, etc.
The display shows three pieces of information:
the alarm indication
the alarm code
the number of minutes the pump has been connected to the
power supply after the alarm occurred.
Warning log (1.10-1.14)
In case of a "warning", the last five warning indications will
appear in the warning log. "Warning log 1" shows the latest fault,
"Warning log 2" shows the latest fault but one, etc.
The display shows three pieces of information:
the warning indication
the warning code
the number of minutes the pump has been connected to the
power supply after the warning occurred.
21

Advertisement

Table of Contents
loading

Table of Contents