Technical data
Fuses
Non-UL fuses and conductor cross-section to mains and motor
Typical shaft
Maximum
power P2
fuse size
[kW]
[A]
1 x 200-240 V
1.1
20
1.5
30
2.2
40
3
40
3.7
60
5.5
80
7.5
100
3 x 200-240 V
0.75
10
1.1
20
1.5
20
2.2
20
3
32
3.7
32
5.5
63
7.5
63
11
63
15
80
18.5
125
22
125
30
160
37
200
45
250
3 x 380-500 V
0.55
10
0.75
10
1.1
10
1.5
10
2.2
20
3
20
4
20
5.5
32
7.5
32
11
63
15
63
18.5
63
22
63
30
80
37
100
45
125
55
160
75
250
90
250
110
300
132
350
160
400
200
500
250
600
3 x 525-600 V
48
Maximum conductor
Fuse
type
cross-section
2
[AWG] (mm
)
–
12 (4)
–
8 (10)
–
8 (10)
–
8 (10)
–
8 (10)
–
8 (10)
–
2 (35)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
8 (10)
gG
8 (10)
gG
8 (10)
gG
2 (35)
gG
1 (50)
gG
1 (50)
gG
1 (50)
aR
3/0 (95)
aR
4/0 (120)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
8 (10)
gG
8 (10)
gG
8 (10)
gG
2 (35)
gG
2 (35)
gG
1 (50)
gG
1 (50)
gG
1 (50)
aR
3/0 (95)
aR
4/0 (120)
gG
2 x 70
gG
2 x 70
gG
2 x 185
gG
2 x 185
gR
2 x 185
Typical shaft
Maximum
power P2
fuse size
[kW]
[A]
0.75
10
1.1
10
1.5
10
2.2
20
3
20
4
20
5.5
32
7.5
32
3 x 525-690 V
11
–
15
–
18.5
–
22
–
30
–
37
–
45
–
55
–
75
–
90
–
110
225
132
250
160
350
200
400
250
500
Grundfos CUE
Maximum conductor
Fuse
type
cross-section
2
[AWG] (mm
)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
gG
12 (4)
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
2 x 70
–
2 x 70
–
2 x 185
–
2 x 185
–
2 x 185