Electrical connection
7.2
Electrical connection
The MA
204i
The voltage supply (PWR IN) as well as the switching inputs/outputs (PWR OUT or PWR IN)
are connected there. The number and function of the switching inputs/outputs is dependent
on the connected end device. Two additional M 12 connectors/sockets are used for connec-
tion to the fieldbus. Both of these connections are B-coded.
An internal RS 232 interface is used for connecting the respective Leuze device. Another
internal RS 232 interface functions as a service interface for configuring the connected
device via a serial null modem cable.
PWR IN
SWIO_2
2
GND
3
5
4
FE
SWIO_1
M 12 connector
(A-coded)
Figure 7.2:
Described in detail in the following are the individual connections and pin assignments.
7.2.1
PWR IN – voltage supply / switching input/output
PWR IN
SWIO_2
GND
3
FE
SWIO_1
M 12 connector
(A-coded)
Table 7.1:
Notice!
The designation and function of the SWIO depends on the connected device. Please observe
the following table!
28
features two M 12 connectors/sockets for voltage supply; each is A-coded.
PWR OUT
SWIO_2
2
VIN
1
VOUT 1
3
5
4
SWIO_1
M 12 socket
(A-coded)
Connections of the MA 204 , view: laying on mounting plate
PWR IN (5-pin connector, A-coded)
Pin
1
2
2
3
VIN
1
5
4
4
5
Thread
Pin assignment PWR IN
LEUZE Device
GND
FE
Name
VIN
Positive supply voltage +18 ... +30 V DC
SWIO_2
GND
SWIO_1
FE
FE
MA
204i
HOST / BUS IN
A (N)
2
GND
N.C.
3
1
485
5
4
FE
B (P)
M 12 connector
(B-coded)
Remark
Switching input/switching output 2
Negative supply voltage 0 V DC
Switching input/switching output 1
Functional earth
Functional earth (housing)
Leuze electronic
BUS OUT
A (N)
2
GND
VP 1
3
5
485
4
FE
B (P)
M 12 socket