Quell QPI9010 Manual page 5

Dual sensor (photoelectric/ionisation) smoke alarm & hush
Table of Contents

Advertisement

0475-7214-06_QPI9010(130417):_
2015.5.22
2:12 PM
Page
Installation
Figure 2A
CEILING
30 cm (12 in)
MINIMUM
DO NOT INSTALL
BEST
PLACEMENT
ACCEPTABLE
PLACEMENT
SIDE WALL
500mm
NOT IN
THIS AREA
1000mm
DEAD AIR
ANYWHERE IN THIS
AREA
DO NOT INSTALL
PEAK CEILING
Figure 2B
500mm
NOT IN
THIS AREA
1000mm
ANYWHERE IN THIS
DEAD AIR
AREA
Smoke alarm should
be located between
500mm and 1500mm
DO NOT INSTALL
of the highest point.
SLOPED CEILING
3
4