b) Positions after Alarm
The position the shutter and blinds assume when an alarm is terminated is also possible to determine by
setting the desired value in the parameter "Status after alarm". The shutter and blinds will remain in
alarm position when the alarm is terminated if the parameter is set to "Maintain"; setting the parameter to
"Previous status" will set the shutter and blinds to the position it was just before the beginning of the
alarm; if the parameter is set to "Theoretical status without alarm", once the alarm is terminated the
shutter and blinds will go to the position they would be in case the alarm hadn't occurred (the last request
related with shutter and blinds positioning is kept); it's possible to "close" (shutter 100% and blinds 180°)
after alarm or to "open" (shutter 0% and blinds 0°).
c) Alarm input mode
The alarm can be indicate active with '1' and inactive with '0' if the parameter "Alarm active if" is set to
"On"; alarm active with '0' and inactive with '1' if the parameter is set to "Off".
User's Manual
4 Detailed Functions Description
Page 38