7
Allow timer reset?
7
Timer expiration Pre-Warning
usage
8
Timer expiration pre-warning The
9
Pre-warning message type
7
Timer Delay change via Com.
Obj.
7
Time Limited Toggle Switch
10
"On/Off" Com.Obj. Function
11
On Delay amount
12
Off Delay amount
8
Visible if "Timer Pre-Warning expiration usage" is set to value different than "Not used".
9
Visible if "Timer Pre-Warning expiration usage" is set to "Send Message via Pre-Warning CO" or "
Message + Invert output
10 The operation of Time Limited Toggle Switch is not affected by the previous parameters.
11 Visible if "''On/Off'' Com.Obj. Function" set to "Delayed On (immediate Off)" or "Delayed On/Off".
12 Visible if "''On/Off'' Com.Obj. Function" set to "Delayed Off (immediate On)" or "Delayed On/Off".
User's Manual
Defines if the delay time is reset when a
Start message arrives.
Defines how the timer expiration warning
shall be issued.
amount
of
expiration that the warning must be
issued.
Defines the type of message to send via
"Pre-Warning" CO.
Defines if the timer's delay time can be
changed via communication object, and
which is the Datapoint Type of the CO.
Defines the delay time for the switch-Off
when
using
the
Toggle Switch" CO.
Defines the behaviour of the device upon
messages on the "On / Off" CO.
Defines the amount of delay to apply
between "On" message arrival and
switching the channel.
Defines the amount of delay to apply
between
"Off" message arrival
switching the channel.
"
4 Detailed Functions Description
Possible values:
*No
Yes
Possible values:
Not used
Send Message via Pre-Warning CO
*Invert output (during 1s)
Send Message + Invert output
time
before
timer
Possible values:
*15s, 30s, ... 2min, 5min, 10min, ...
Possible values:
*On
Off
Possible values:
*Not used
DPT7.005 TimePeriodSec
DPT9.010 TimeValue
Possible values:
1s, 2s, [+1s]... *10s, ... 1min, 1min
"Time
Limited
Possible values:
*On / Off
Delayed On (immediate Off)
Delayed Off (immediate On)
Delayed On / Off
Timer On
Timer Off
Possible values:
1s, 2s, [+1s]... *10s, ... 1min, 1min
Possible values:
and
1s, 2s, [+1s]... *10s, ... 1min, 1min
20min
(PDTUNSIGNED_INT)
(PDT_KNX_FLOAT)
15s, [+15s] .... 2min, 3min,
[+1min]...
15min,
20min,
[+15min]... 1h, 2h, [+1h]...
1day
15s, [+15s] .... 2min, 3min,
[+1min]...
15min,
20min,
[+15min]... 1h, 2h, [+1h]...
1day
15s, [+15s] .... 2min, 3min,
[+1min]...
15min,
20min,
[+15min]... 1h, 2h, [+1h]...
1day