Makel MSA-CM Series User Manual page 30

Table of Contents

Advertisement

Figure 10: Channel's General configuration page (shutter and blinds).
Table 7: Parameters in General configuration page for Shutter and Blinds.
Parameter
Control also Blinds
18
Blinds step time (x10ms)
18
Number of blinds steps
18
Blinds position control CO type
Time for complete up movement
(s)
Time
for
complete
movement (s)
18 Visible is "Control also Blinds?" set to "Yes".
User's Manual
Description
Defines if the system to be controlled
also includes blinds.
Defines the length of one blinds' step.
The value is multiplied per 10ms.
Defines the number of steps (with the
defined length) are needed for a full
movement of the blinds.
Defines which datapoint type is to be
used for control the blinds position.
Defines the amount of time it takes for
the shutter to go from totally closed to
totally opened.
down
Defines the amount of time it takes for
the shutter to go from totally opened to
totally closed.
4 Detailed Functions Description
Values
Possible values:
*No
Yes
Min: 5 (50 ms)
Max: 255 (2550 ms)
Default: 20 (200ms)
Min: 1
Max: 255
Default: 10
Possible values:
*Angle [DPT_ID Angle 5.003]
Percentage [DPT_ID Scaling 5.001]
Min: 1
Max: 65535
Default: 120
Min: 1
Max: 65535
Default: 120