Type Codes for Output Devices

7\SH&RGHVIRU2XWSXW'HYLFHV
AFC-600 Programming PN 51032:A 3/8/99
Technical Manuals Online! - http://www.tech-man.com
2YHUYLHZ
This section provides Type Codes for control modules, NACs, and Panel Circuits. For
instructions on programming Type Codes, refer to "How to Modify or Delete a Point
(2=
)" on page 21.
POINT
7\SH&RGHVIRU&RQWURO0RGXOHV
Table 47 contains a comprehensive list of control module Type Codes, which you can
select to change the function of a control module point. The Type Codes that display,
however, depend on the configuration.
Type Code
Configuration
NAC
CONTROL
Form-C relay
RELAY
NAC
BELL CIRCUIT
NAC
STROBE CKT
NAC
HORN CIRCUIT
NAC
AUDIBLE CKT
NAC
SPEAKER
NAC
REL END BELL
blank label
NAC
NAC
RELEASE CKT
NAC
REL CKT ULC
.
Form-C relay
RELEA
FORM C
NAC
REL AUDIBLE
Form-C relay and
NONRESET CTL
NAC
NAC
TELEPHONE
NAC
INSTANT RELE
7DEOH  &RQWURO 0RGXOH 7\SH &RGHV
$SSHQGL[ * 7\SH &RGHV
Function
Supervised NAC
Relay output
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC (use when no other Type
Code applies)
Releasing Circuit, nonpower-limited,
supervised for opens and ground faults
(always non-silenceable)
Releasing circuit, power-limited,
supervised for opens, shorts and ground
faults
Relay output, contacts operate upon release
NAC, activated upon release
Relay output, unaffected by "System
Reset" command
Standard telephone circuit
NAC, short=normal; supervised for open
circuits and ground faults. Always non-
silenceable and switch-inhibited.
99