This section provides details for programming the releasing functions: Delay Timer,
Abort Switch, Cross Zone, and Soak Timer.
+RZWR3URJUDPD'HOD\7LPHU
Use a Delay Timer to specify the elapsed time between alarm activation of an initiating
device and activation of all output devices mapped to that device. You can set the Delay
Timer from 0 to 60 seconds. For example, Figure 58 shows graphical representation of
a 15-second timer:
,QLWLDWLQJ GHYLFH V
0
LQ 5HOHDVLQJ =RQH
4 5
5 DFWLYDWHV
3 0
)LJXUH  ([DPSOH RI 6HFRQG 'HOD\ 7LPHU
To program a Delay Timer, enter a 0-60 second value as shown in "R0-R9 (Releasing
Functions)" on page 30.
+RZWR3URJUDPDQ$ERUW6ZLWFK
The control panel provides four types of Abort Switches (ULI, IRI, NYC, and AHJ)
that you can use, that will affect the operation of a Delay Timer mapped to the same
Releasing Zone. For example, an Abort Switch selected for Releasing Zone R05 only
affects the Delay Timer selected for R05. Other requirements for using an Abort Switch
include the following:
Connecting an monitor module to a UL-listed abort station, such as the N-ARA-10
shown in Figure 59.
Program the monitor module with the Type Code
to Program a Monitor Module" on page 23).
Abort switch shall not be used with a preaction system.
)LJXUH  1$5$ 8/OLVWHG $ERUW 6WDWLRQ
This section contains information for programming each type of Abort Switch for a
Releasing Zone.

How to Program a Releasing Zone

'HOD\

 VHFRQGV
15
ABORT SWITCH
AFC-600 Programming PN 51032:A 3/8/99
0
$OO RXWSXWV
45
1 5
5HOHDVLQJ =RQH 5
3 0
. (Refer to "How
$ERUW 6ZLWFK
0DQXDO $JHQW
5HOHDVH OHYHU
Continued on the next page...