Type Codes For Input Devices - Notifier AFC-600 Programming Manual

Intelligent fire panel
Hide thumbs Also See for AFC-600:
Table of Contents

Advertisement

$SSHQGL[ * 7\SH &RGHV
7\SH&RGHVIRU,QSXW'HYLFHV
1RWH
$ UHIHUHQFH GHWHFWRU VWLOO
IXQFWLRQV DV D VPRNH GHWHFWRU
EXW \RX VKRXOG VHW WKH GHWHFWRU
VHQVLWLYLW\ OHYHO WR WKH OHDVW
VHQVLWLYH OHYHO³$/ DQG
3$&KDQJH $ODUP DQG
3UH$ODUP VHQVLWLYLW\
5HIHU WR ´'HWHFWRU 6HQVLWLYLW\
6HWWLQJVµ RQ SDJH  IRU D
FRPSOHWH OLVW RI GHWHFWRU
VHQVLWLYLW\ VHWWLQJV
96
Technical Manuals Online! - http://www.tech-man.com
2YHUYLHZ
This section provides Type Codes for intelligent detectors and monitor modules. For
instructions on programming Type Codes, refer to "How to Modify or Delete a Point
(2=
)" on page 21.
POINT
7\SH&RGHVIRU,QWHOOLJHQW'HWHFWRUV
Table 45 contains a list of intelligent detector Type Codes, which specify the type of
detector installed at an SLC address.
Type Code
Point Function
alarm point that
ION
activates CBE
supervisory point
SUPERV DUCTI
that activates CBE
alarm point that
PHOTO
activates CBE
supervisory point
SUPERV DUCTP
that activates CBE
alarm point that
LASER
activates CBE
alarm point that
AIR REF DET
activates CBE
alarm point that
MULTI
activates CBE
(analog)
alarm point that
HEAT
activates CBE
7DEOH  ,QWHOOLJHQW 'HWHFWRU 7\SH &RGHV

Type Codes for Input Devices

Function
Ionization detector (CPX series)
Assign to an ion detector that is used as a duct
detector to report a supervisory condition rather
than an alarm
Photoelectric smoke detector (SDX series)
Assign to a photo detector that is used as a duct
detector to report a supervisory condition rather
than an alarm
Laser smoke detector (LPX series)
Assign to one or more LPX-751 detectors used to
monitor the quality of air entering the protected
area. The air quality measurement allows the
VIEW system to compensate for vehicle fumes,
fog, or other particles brought into the protected
area through the ventilation system. Poor air
quality will lower the sensitivity of all LPX-751
detector on the SLC. The detector sensitivity,
however, remains within approved limits (always
less than 1% obscuration per foot).
Multisensor smoke detector (IPX series)
Heat detector (FDX series)
AFC-600 Programming PN 51032:A 3/8/99