Time Control Zones

7LPH&RQWURO=RQHV
1RWH
$OO DFWLYH 7LPH &RQWURO
RXWSXWV ZLOO WXUQ RII WHPSRUDULO\
ZKLOH UHVHWWLQJ RU SURJUDPPLQJ
WKH FRQWURO SDQHO
&RGLQJ)XQFWLRQVIRU1$&6DQG3DQHO&LUFXLWV
1RWH
'R QRW LQFOXGH ) LQ WKH
&%( OLVW RI 1$&V DQG 3DQHO
&LUFXLWV XVHG IRU UHOHDVLQJ RU
]RQH FRGLQJ DSSOLFDWLRQV
AFC-600 Programming PN 51032:A 3/8/99
Technical Manuals Online! - http://www.tech-man.com
All outputs with a CBE list containing F5 or F6 activate within the times specified for
the days of the week listed in F5 or F6. All smoke detectors with a CBE list containing
F5 or F6 switch to their lowest sensitivity (AL:9) within the times specified for the days
of the week listed in ZF5 or ZF6. Refer to "Appendix C: AWACS Applications" on
page 73 for details on setting detector sensitivity.
Time Control is active for all days of the week listed in F5 or F6. Holidays listed in F7
are excluded unless you list Holidays (H) in the day-of-week selection of F5 and F6.
Enter the time in a 24-hour format with the OFF time later than the ON time. After
changing programming using Time Control, always reset the control panel.
Coding Functions are pulsed signals that you can select, using Special Zone F8, to
energize NACs and Panel Circuits when a fire alarm activates. NACs and Panel Circuits
with a CBE list that includes F8 energize when activated by a fire alarm. Before
selecting an output circuit for a two-stage Coding Function, note the following:
1
NAC and Panel Circuits activated exclusively by an initiating device with a
Type Code turn a steady even if selected for a Coding Function
HAZARD ALERT
1
The control panel automatically sends an Alert signal to any of the four NACs
mapped to Z00 and F8, but not mapped to the alarm signal. After 5 minutes
without an acknowledge or silence, the Alert signal becomes steady.
Select Coding Functions on a global basis, through Special Zone F8. That is, all NACs
and Panel Circuits selected for Coding Functions, will sound the same code when
activated. Table 36 contains descriptions of each Coding Function selection:
Coding Function
Selection
March Time (default)
1
Two-Stage
California
Temporal
7DEOH  &RGLQJ )XQFWLRQ 6HOHFWLRQV
$SSHQGL[ % 6SHFLDO =RQH 2XWSXWV
Signal
120 ppm (pulses per minute)
Alert signal – 20 PPM;
general alarm signal: steady tone
10 sec. On, 5 sec. Off, repeats
0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off, repeats
71