What are Releasing Zones?

:KDWDUH5HOHDVLQJ=RQHV"
1RWH
5HOHDVLQJ =RQHV 55
DSSHDU LQ WKH &%( OLVW RI GHYLFHV
DV =5=5 )RU H[DPSOH LI \RX
OLVW 5 IRU D GHWHFWRU RQH RI WKH
ILYH ]RQHV LQ WKH &%( OLVW RI WKH
GHWHFWRU ZLOO GLVSOD\ DV =5
1RWH
)RU GHWDLOHG LQIRUPDWLRQ
RQ WKH IRXU UHOHDVLQJ IXQFWLRQV
UHIHU WR +RZ WR 3URJUDP D
5HOHDVLQJ =RQH RQ SDJH 
1)3$5HOHDVLQJ$SSOLFDWLRQV
AFC-600 Programming PN 51032:A 3/8/99
Technical Manuals Online! - http://www.tech-man.com
$SSHQGL[$5HOHDVLQJ$SSOLFDWLRQV
WARNING: When used for CO2 releasing applications, observe proper precautions as
stated in NFPA 12. Do not enter the protected space unless physical lockout and other
safety procedures are fully completed. Do not use software disable functions in the
panel as lockout.
The control panel includes ten Releasing Zones (R0-R9) that you can use to control up
to ten releasing operations. Each Releasing Zone operates independently, and is fully
programmable. From the Special Function Change Screen (Figure 30 on page 29),
select a Releasing Zone (R0-R9) to display the Releasing Function screen:
Each Releasing Zone includes four releasing functions, outlined in Table 27:
Function
Lets You
Delay
Program a 0-60-second Delay Timer. The Delay Timer equals the time that must
elapse between activating an initiating device and activating the releasing zones
mapped to the active initiating device.
Abort
Select a 3-letter Abort switch Type Code (ULI, IRI, NYC, or AHJ) that adds a
delay time to a Releasing Zone, or prevents a release of a Releasing Zone ("How
to Program an Abort Switch" on page 46).
Cross
Select one of three Cross Zone types or "N" (not used). A Cross Zone requires
tripping two or more devices to activate the outputs mapped to one of the
Releasing Zones.
Soak
Select a Soak Timer (0-9999 seconds) or "0" (not used).
You can use the AFC-600 as a control panel for agent release or preaction/deluge
control applications. When used with compatible, UL-listed actuating and initiating
devices, the control panel meets the requirements of the following NFPA standards:
Standard
NFPA 12
NFPA 12A
NFPA 12B
NFPA 13
NFPA 15
NFPA 16
NFPA 17
NFPA 17A
NFPA 2001
7DEOH 
35* 5(/($6( )81&7
5(/($6( &21752/
'(/$<  $%257 8/, &5266 1 62.  5
)LJXUH  5HOHDVLQJ )XQFWLRQ 6FUHHQ
7DEOH  5HOHDVLQJ )XQFWLRQV
Covers
CO2 Extinguishing Systems
Halon 1301 Extinguishing Systems
Halon 1211 Extinguishing Systems
Sprinkler Systems
Water Spray Systems
Foam-water Deluge and Foam-water Spray Systems
Dry Chemical Extinguishing Systems
Wet Chemical Extinguishing Systems
Clean Agent Fire Extinguishing Systems
1)3$ 6WDQGDUGV IRU 5HOHDVLQJ $SSOLFDWLRQV
$SSHQGL[ $ 5HOHDVLQJ $SSOLFDWLRQV
45