Global System Functions - Notifier AFC-600 Programming Manual

Intelligent fire panel
Hide thumbs Also See for AFC-600:
Table of Contents

Advertisement

 3URJUDP &KDQJH
&
3URJUDP &KDQJH
SDVVZRUG
&

)
WR H[LW
*OREDO 6\VWHP )XQFWLRQV
32
Technical Manuals Online! - http://www.tech-man.com
+RZWR&KDQJH*OREDO6\VWHP)XQFWLRQV  6<67(0
The System option lets you select settings for global system functions that apply to all
programmed devices and zones. For instance, selecting an Alarm Verification Timer for
30 seconds means that all initiating devices selected for Alarm Verification use a
30-second timer. From the Program Change screen (Figure 8 on page 15), press the 7
key to display the System Function screen:
6,/ ,1+  $872  9(5,)<  86$ 7,0(
7(50 1 $&B'/< < /RF7 %/,1.  67  $&6 1
)LJXUH  6\VWHP )XQFWLRQ 6FUHHQ
Table 18 contains settings for global system functions.
System Function
SIL INH (Silence Inhibit Timer)
AUTO (Auto Silence Timer)
VERIFY (Alarm Verification Timer)
USA TIME
TERM – Allows supervision for devices
connected to TB3, i.e. LCD-80.
AC_DLY=Y
LocT Terminal mode – one of three
operating modes of PC or terminal
connected to the control panel through
TB2 on the CPU.
Note: For a complete list of functions,
refer to the AFC-600 Installation Manual.
BLINK=01 (addressable SLC device
LED blink)
ST=4 – the NFPA wiring style used for
the SLC.
ACS – Use ACS Selection Groups (Refer
to "Annunciator Options" on page 33).
7DEOH  6HWWLQJV IRU *OREDO 6\VWHP )XQFWLRQV
How to Use the Basic Program
Setting
0 to 300 seconds
000 (none)
600 to 900 seconds
0 to 30 seconds
USA time (mm/dd/yy) or
EUR time (dd/mm/yy)
Press the
or
key to
NEXT
PREVIOUS
change. Note that (European) time
changes to 24-hour time format
and date format
N no supervision
Y supervision enabled
AC delay – delays loss of AC
reporting for 8 hours.
Y=AC delay
N=no AC delay
LocT (terminal connected
to control panel and
located in same room)
LocM (same as LocT but
requires password)
RemT (terminal connected
through a modem for Read
Status only)
Blink - Select from 00 to 16.
(00 = no blink, 01 = blink every
poll, 02 = blink every 2nd poll, 03
= blink every 3rd poll up to 16 =
blink every 16th poll) - Note: this
setting effects FlashScan devices
only.
ST=6 (Style 6 SLC wiring)
ST=4 (Style 4 SLC wiring)
N or Y
AFC-600 Programming PN 51032:A 3/8/99
Default
000
000
30
USA TIME
N0
Y
LocT
01
ST=4
ACS=N