Chapter 8 High-speed Link
8) Setting of High-speed link block
Double-click the applicable index number of Configuration file uploaded and designates the 'Read
area' and 'Save area'.
Classification
Master
Display the Master station no.
Station No.
Setting range for the slave : 0 ~ 126
Station No. *1
If identical station No. is set, communication will not be normal.
Send: Transmission the data from master module to slave module.
Mode *1
Receive : Transmission the data from slave module to master module.
Read area
(Master module
Slave module)
Save area
(Slave module
Master module)
Sending data
Display input/output points of slave module by the bytes.
Receiving data
- In case of I/O module of 8 bits or less, please set 1 byte.
(Byte)
*1 : Area is not able to set
8
Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User's Guide
[Figure 8.4.5] Setting of High-speed link block
Area to set the start address of device used for Sending.
2MLK
Setting device : P, M, K, F, T, C, U, Z, L, N, D, R, ZR
Area to set the start address of device used for Sending.
2MLI
Setting device : A, M, I, Q, R, W, F, K, L, N, U
Area to set the start address of device used for Receiving.
2MLK
Setting device : P, M, K, F, T, C, U, Z, L, N, D, R, ZR
Area to set the start address of device used for Receiving.
2MLI
Setting device : A, M, I, Q, R, W, F, K, L, N, U
[Table 8.4,3] Setting of High-speed link block