Appendix
Notes
HS link No.
2
L000500~L00099F
3
L001000~L00149F
4
L001500~L00199F
5
L002000~L00249F
6
L002500~L00299F
7
L003000~L00349F
8
L003500~L00399F
9
L004000~L00449F
10
L004500~L00499F
11
L005000~L00549F
Ex.)
K as a block number is displayed through 8 words by 16 for 1 word for the information of 128 blocks from 000
to 127.
For example, block information of 16~31, 32~47, 48~63, 64~79, 80~95, 96~111, 112~127 will be displayed in
L00011, L00012, L00013, L00014, L00015, L00016, L00017 from block 0 to block 15 for mode information
(_HS1MOD). Thus, the mode information of the block No. 55 will be displayed in L000137.
A - 4
Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User's Guide
L area address
Compared with HS link of 1 in [Table 1], other HS link station number's
flag address will be simply calculated as follows;
 Calculation formula:
L area address = L000000 + 500 x (HS link No. – 1)
In order to use HS link flag for program and monitoring, use the flag
map registered in SoftMaster for convenient application..
Honeywell
Remarks
January 2019
R220