CAUTION—Hazard or unsafe practice which COULD result in minor injury or in product or property damage. SAFETY DXR Series dryers are designed and built with safety as Safety Labels a prime consideration; industry-accepted safety factors Dryer labels providing important safety information are have been used in the design.
When an oil-removal filter is placing material. Claim filing and processing is your re- used, install the filter downstream of the DXR Series sponsibility. dryer. At this location, the life of the replaceable filter element is prolonged since some of the entrained oil is removed by the dryer and drained through the separator.
4800 HOW IT WORKS Air Flow DXR Series dryers use refrigeration cooling to condense entrained moisture out of the airstream (see Figure 2). Warm saturated air enters the air- to-air heat exchanger where it is cooled by outgoing cold air. The inlet air is further cooled in the refrigeration chiller.
• drain valve controls The SCAN/SEEK push button on the System Operation Monitor provides a readout on the alphanumeric display • temperature sensor probes of the following temperatures: • inlet air Figure 4. System Operation Monitor DXR Series Dryers (Bulletin 553)
Page 7
System Alarm indi- frigerant discharge and ambient air. To stop the scan cator will flash. Refer to the Field Service Guide in this mode push the TIME ADJUST button once. DXR Series Dryers (Bulletin 553)
Page 8
Normal temperature range is indicated by a 3-second red light. The red light flashes when temperatures are outside the normal range. Dew points 50°F or higher may cause the REFRIG. SUCTION signal to flash. See the Field Service Guide if red lights flash. DXR Series Dryers (Bulletin 553)
* Water or Ambient is displayed, based on ver- a second time. The display will show the current setting sion. for the ADV open time. DXR Series Dryers (Bulletin 553)
2. Confirm that condensate is discharging from the automatic drain valves and that the condensate 1. Turn off the power switch. lines from the automatic drain valve discharge into 2. Disconnect the main power supply. DXR Series Dryers (Bulletin 553)
MAINTENANCE duce the cooling efficiency, clean the coil. DXR Series dryers require little maintenance for satis- Replace the ambient air filter. See Ambient Air Filter factory operation. Good performance can be expected if Replacement procedure.
30 psig. Servicing 4. Check that small port in diaphragm assembly is All DXR Series dryers have a timer-controlled auto- clear and solenoid coil moves freely in housing. Vi- matic drain valve.The valve body is mounted on the ton diaphragm seals are compatible with commonly frame bottom;...
Page 13
CAUTION Lubricate the O-ring with a petroleum-based lubricant compatible with your application. 8. Lightly lubricate the filter bowl O-ring. Figure 7 Side view of coalescing filter DXR Series Dryers (Bulletin 553) 1-11...
Burning mate rials may decompose refrigerants, forming toxic gas or acids that may cause serious injury and property damage. The refrigerant valves are adjusted at the factory with the refrigerant system operating and no airflow through 1-12 DXR Series Dryers (Bulletin 553)
Page 15
3. Check airflow and system capacity. Re- duce airflow or resize and replace system. 4. Leak in refrigeration system. 4. Locate leak; repair and recharge. Refrigerant discharge Low ambient temperature. Consult your local distributor. temperature lower than 140°F. DXR Series Dryers (Bulletin 553) 1-13...
Page 16
2. Timer malfunction. 2. Replace timer assembly. Digital display Display blank Temporary loss of power Stop unit for 10 minutes; then restart. not working Drain not working or drain cycling fast 1-14 DXR Series Dryers (Bulletin 553)
Page 17
5 psi pressure drop. Pressure drop may exceed 5 psi when the dryer is sized for a dew point higher than 33°F-39°F. Contact your local distributor for estimated pressure drop at nonstandard operating conditions. Refer to dryer data plate for refrigerant charge. DXR Series Dryers (Bulletin 553) 1-15...
ADVERTENCIA y PRECAUCION se usan para INTRODUCCION indicar el nivel de gravedad del peligro, como sigue: Los secadores refrigerados de aire comprimido de la PELIGRO — Peligro Inmediato que CAUSARA Serie DXR utilizan la refrigeración mecánica para secar heridas graves o muerte. el aire comprimido hasta puntos de rocío tan bajos como 33°F-39°F.
han sido dañados o se han perdido durante el tránsito, Por seguridad y conveniencia, instale válvulas de corte usted lo hace bajo su propio riesgo y responsabilidad. y de despresurización a la entrada y a la salida en los sitios indicados. Estas válvulas permiten que el secador El fabricante está...
nacionales, para prevención de incendios, de seguridad Modelos Enfriados por Aire y eléctricos. La instalación debe estar de acuerdo con el El aire de refrigeración debe ser tomado de un área Código Eléctrico Nacional. Confirme que su voltaje de despejada y bien ventilada para reducir la acumulación línea sea el mismo que el voltaje listado en la placa de de suciedad y polvo en el serpentín del condensador.
A medida que se devuelve por el intercambiador de • Luces indicadoras calor aire a aire, el aire frío es calentado nuevamente • pantalla alfanumérica por el aire caliente que entra. El uso del aire saliente para pre-enfriar el aire admitido condensa el 65 por •...
La pantalla puede ser programada para mostrar Campo en este manual si la lectura de cualquier automáticamente cada temperatura durante cinco temperatura se sale del rango normal. segundos en secuencia o para mostrar continuamente Temperatura del Aire de Admisión — Si la cualquier lectura seleccionada.
Page 26
Tabla 3 LUCES INDICADORES DEL MONITOR DE OPERACION DEL SISTEMA INDICA ACCION REQUERIDA NOTAS INDICADORA La temperatura dentro del evaporador Este indicador debe iluminarse dentro de El indicador se apagará si NORMAL (enfriador) es normal. los treinta minutos del arranque, después el indicador de CHECK OPERATION de que el sistema de refrigeración se...
• “,” = caracter coma Tabla 4 TEMPERATURA INTERMEDIA DEL AIRE • cr = retorno de carro FLUJO DE AIRE RANGO NORMAL APROXIMADO DE ENTRADA AL • lf = avance de línea SECADOR Punto de Rocío Punto de Rocío (% de la capacidad 33°F - 39°F 50°...
• L = bits de alarma CLOSED/OPEN una vez. Espere unos segundos a que el monitor se restablezca y luego presione el botón por • S = indicación de “necesidad de servicio” segunda vez. La pantalla mostrará la programación ac- Los caracteres hexadecimales (HEX) después de la “L”...
Para arrancar el secador: El secador está diseñado para operar continuamente. Deje que el secador opere aún cuando la demanda de 1. Posicione el interruptor de encendido en la posición aire comprimido sea interrumpida; el secador no se ON. El compresor de refrigerante arrancará. El congelará.
mantenimiento correctivo durante el período de • Desensamble y limpie el recipiente del separador garantía, llame a su distribuidor local y proceda de • Para los condensadores enfriados por aire, acuerdo a sus instrucciones. Refiérase a la garantía para inspeccione los serpentines del condensador y los límites de su cubrimiento.
Para desensamblar las ADVs para su limpieza u otro 1. Inspeccione el diafragma; límpielo o reemplácelo mantenimiento: según sea necesario. 1. Apague el interruptor de potencia. 2. Remueva las partículas del cuerpo de la válvula. 2. Desconecte el suministro principal de potencia al 3.
Page 32
Date Element Changed: con la informacion actualizada Changed By: Next Scheduled Change: debe ser colocada sobre la Additional elements available from your local Ingersoll-Rand Compressed Air System supplier calcomania anterior cada vez que Telephone: Fax: el elemento sea reemplazado. Figura 7...
presión/temperatura de succión, un mecánico en GUÍA PARA EL SERVICIO EN EL refrigeración debe instalar un conjunto de medidores en CAMPO la unidad. La lectura en los medidores debe ser como Los problemas encontrados con más frecuencia en los sigue: secadores refrigerados son, agua después del secador y Tabla 6 caídas excesivas de presión.
Page 34
GUÍA PARA SERVICIO EN EL CAMPO PROBLEMA SINTOMA(S) POSIBLE CAUSA SOLUCION No hay descarga de las válvu- Falla de la ADV o acumulación de Desmantele la ADV; limpie, repare o reem- las automáticas de drenaje suciedad en la ADV. place. Ver sección de Mantenimiento. (ADVs).
Page 35
PROBLEMA SINTOMA(S) POSIBLE CAUSA SOLUCION 1. Ajuste inapropiado de la HGBV. 1. Remueva la tapa de la HGBV y desatorn- ille la HGVB media vuelta usando un llave allen para bajar la temperatura de succión hasta el nivel listado en la sección de Flujo de Refrigerante.
Page 36
PROBLEMA SINTOMA(S) POSIBLE CAUSA SOLUCION Temperatura de descarga del Agua en el sistema de refrigera- Localice la fuga. Repare la fuga o reem- refrigerante es mayor a ción. Fuga en el enfriador o en el place el enfriador o el condensador. Alta temperatura 220°F.
Page 37
Tabla 8 DIMENSIONES E TAMAÑOS DE LAS CONEXIONES DIMENSIONES PRESION DE OPERACIÓN CONEXIONES ENT-SAL (pulg) MODELO NO. MAX (psig) (pulg NPT) DXR425 DXR600 DXR800 DXR1000 Tabla 9 ESPECIFICACIONES DE LOS SECADORES RANGO POTENCIA DEL POTENCIA CAPACIDAD SUMINISTRO PERMISIBLE COMPRESOR MODELO DE TIPO DE NOMINAL DE POTENCIA...
Air-cooled models only.(Sólo para modelos enfriados por aire.) Water-cooled models only. (Sólo para modelos enfriados por água.) Electrical components listed are for standard voltage units. (Los componentes eléctricos listados son para unidades con voltaje estándar.) DXR Series Dryers (Bulletin 553)
Page 41
Air-cooled models only.(Sólo para modelos enfriados por aire.) Water-cooled models only. (Sólo para modelos enfriados por água.) Electrical components listed are for standard voltage units. (Los componentes eléctricos listados son para unidades con voltaje estándar.) DXR Series Dryers (Bulletin 553)
Page 42
Refrigeration Flow Schematic (Esquema de Flujo de Refrigerante) DXR425 – DXR600 DXR Series Dryers (Bulletin 553)
Page 43
Refrigeration Flow Schematic (Esquema de Flujo de Refrigerante) DXR425W – DXR600W DXR Series Dryers (Bulletin 553)
Page 44
Refrigeration Flow Schematic (Esquema de Flujo de Refrigerante) DXR800 – DXR1000 DXR Series Dryers (Bulletin 553)
Page 45
Refrigeration Flow Schematic (Esquema de Flujo de Refrigerante) DXR800W – DXR1000W DXR Series Dryers (Bulletin 553)
Page 46
DXR425-A – DXR1000-A DXR Series Dryers (Bulletin 553)
Page 47
DXR425-W – DXR1000-W DXR Series Dryers (Bulletin 553)