Repair Procedures - Daikin Stylish Series Service Manual

Split stylish r32
Hide thumbs Also See for Stylish Series:
Table of Contents

Advertisement

2 Components
To perform an electrical check of the expansion
valve
Prerequisite: First perform a mechanical check of the expansion
valve, see
"2.3.1 Checking procedures" on
1 Make sure that the electrical connector of the expansion valve
motor is correctly connected to the main PCB.
2 Disconnect the electrical connector of the expansion valve
motor from the main PCB and measure the continuity between
the following pins (windings) using a multi meter. All
measurements MUST be approximately the same.
▪ Connector pin 1‑6,
▪ Connector pin 2‑6,
▪ Connector pin 3‑6,
▪ Connector pin 4‑6.
a
a
Connector S20
1 or more windings have no
Action
continuity?
Yes
Replace the expansion valve
motor,
procedures" on
No
Component is OK. Return to the
troubleshooting of the specific
error and continue with the next
step.
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
2.3.2

Repair procedures

To remove the expansion valve motor
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
work" on
page 40.
Prerequisite: If needed, remove any parts to create more space for
the removal.
1 Pull up the expansion valve motor to remove it from the
expansion valve body.
INFORMATION
It may be needed to turn the expansion valve motor 1/8
turn counter clockwise to unlock it.
Service manual
24
page 23.
"2.3.2 Repair
page 24.
2 Cut all tie straps that fix the expansion valve motor harness.
3 Disconnect the expansion valve motor connector from the main
4 To install the expansion valve motor, see
To remove the expansion valve body
Prerequisite: Recuperate the refrigerant from the refrigerant circuit,
see
"3.2.2 Repair procedures" on
Prerequisite: If needed, remove any parts to create more space for
the removal.
1 Remove the expansion valve motor, see
2 Remove the putty. Keep for re-use.
"2.13  Plate
a
a
Expansion valve motor
b
Expansion valve motor harness
a
Expansion valve motor
INFORMATION
The expansion valve and motor can have a different
configuration / layout.
PCB.
procedures" on
page 24.
page 54.
procedures" on
page 24.
(C)(F)TXA15~50A2V1B(W)(S)(T) + RXA42+50A2V1B +
b
a
"2.3.2  Repair
"2.3.2  Repair
RXA20~35A2V1B
Split Stylish R32
ESIE18-03 – 2018.09