H0-00 - Current Sensor Abnormality; H3-00 - High Pressure Switch Defect; H6-00 - Location Detection Sensor Abnormality; H8-00 - Compressor Input Abnormality - Daikin Stylish Series Service Manual

Split stylish r32
Hide thumbs Also See for Stylish Series:
Table of Contents

Advertisement

1 Troubleshooting
1.5.20
H3-00 – High pressure switch defect
Trigger
Effect
High pressure switch
Unit will stop
is activated when
operating.
compressor is off.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1 Perform a check of the high pressure switch. See
pressure switch" on
page 27.
Possible cause: Faulty high pressure switch.
2 Perform a check of the refrigerant circuit. See
circuit" on
page 53.
Possible cause:
▪ Stop valve is closed,
▪ Clogged refrigerant circuit,
▪ Refrigerant circuit NOT charged correctly,
▪ Humidity in the refrigerant circuit,
▪ Non-condensables in the refrigerant circuit,
▪ Leaking refrigerant circuit.
3 Perform a check of the main PCB. See
page 35.
Possible cause: Faulty main PCB.
4 Perform a check of the inverter PCB. See
PCB" on
page 34.
Possible cause: Faulty power module = inverter PCB.
5 Check if the power supply is conform with the regulations. See
"3.1 Power supply" on
page 52.
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance
>10%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.5.21
H6-00 – Location detection sensor
abnormality
Trigger
Effect
Compressor fails to
Unit will NOT stop
start within
operating.
15 seconds after the
compressor run
command signal is
If the error re-occurs
sent.
within 8 minutes: unit
will stop operating.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1 Perform a check of the compressor. See
page 20.
Possible cause: Faulty compressor.
2 Perform a check of the main PCB. See
page 35.
Service manual
10
Possible cause: Faulty main PCB.
3 Perform a check of the inverter PCB. See
Reset
PCB" on
Manual reset via user
Possible cause: Faulty power module = inverter PCB.
interface.
4 Perform a check of the refrigerant circuit. See
circuit" on
Possible cause:
▪ Stop valve is closed,
▪ Clogged refrigerant circuit,
▪ Refrigerant circuit NOT charged correctly,
▪ Humidity in the refrigerant circuit,
"2.5  High
▪ Non-condensables in the refrigerant circuit,
▪ Leaking refrigerant circuit.
5 Check if the power supply is conform with the regulations. See
"3.1 Power supply" on
"3.2  Refrigerant
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance
>10%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
"2.11  Main PCB"  on
1.5.22
Trigger
"2.10  Inverter
DC voltage or current
sensor abnormality
based on the
compressor running
frequency and the
input current.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1 Perform a check of the main PCB. See
page 35.
Possible cause: Faulty main PCB.
2 Perform a check of the inverter PCB. See
PCB" on
Reset
Possible cause: Faulty power module = inverter PCB.
Automatic reset after
a continuous
3 Perform a check of the compressor. See
operation of
page 20.
10 minutes.
Possible cause: Faulty compressor.
Manual reset via user
interface.
4 Perform a check of the reactor. See
page 44.
Possible cause: Faulty reactor.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
"2.2  Compressor"  on
"2.11  Main PCB"  on
page 34.
page 53.
page 52.
H8-00 – Compressor input abnormality
Effect
Reset
Unit will NOT stop
Automatic reset when
operating.
compressor runs
normally for
60 minutes.
If the error re-occurs
Manual reset via user
too soon: unit will
interface.
stop operating.
"2.11  Main PCB"  on
page 34.
"2.2  Compressor"  on
"2.14  Reactor"  on
(C)(F)TXA15~50A2V1B(W)(S)(T) + RXA42+50A2V1B +
"2.10  Inverter
"3.2  Refrigerant
"2.10  Inverter
RXA20~35A2V1B
Split Stylish R32
ESIE18-03 – 2018.09