Field Settings; To Control Heating Only Mode; To Adjust Target Set Temperature In Heating Operation; To Control The Indoor Unit Fan During Thermostat Off - Daikin Stylish Series Service Manual

Split stylish r32
Hide thumbs Also See for Stylish Series:
Table of Contents

Advertisement

5.6

Field settings

5.6.1

To control heating only mode

Prerequisite: Stop operation of the unit.
1 Press
,
, and
simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 19.
7 Press
to confirm.
8 Press
.
9 Select 1 (0: factory setting, 1: heating only).
10 Press
to confirm.
5.6.2
To adjust target set temperature in
heating operation
INFORMATION
When there is a big difference between the indoor room
temperature and the set temperature in heating mode,
adjust the target set temperature field setting.
▪ Target temperature = remote controller set temperature +
2.5°C. For example:
Remote controller set temperature = 20°C
Target temperature = 20°C + 2.5°C = 22.5°C
Thermo off temperature = 24.5°C
1 Press
,
, and
simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 7.
7 Press
to confirm.
8 Press
.
9 Select the value to set the desired target temperature:
▪ 0 = –2,0°C
▪ 1 = –1,0°C
▪ 2 = 0°C (factory setting)
▪ 3 = +1,0°C
▪ 4 = +2,0°C
10 Press
to confirm.
5.6.3
To control the indoor unit fan during
thermostat off
1 Press
,
, and
simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 4.
7 Press
to confirm.
(C)(F)TXA15~50A2V1B(W)(S)(T) + RXA42+50A2V1B +
RXA20~35A2V1B
Split Stylish R32
ESIE18-03 – 2018.09
8 Press
.
9 Select 0 (0: fan ON, 1: fan OFF).
10 Press
to confirm.
5.6.4

To change auto restart ON to OFF

INFORMATION
After power failure, the unit will automatically restart
(default setting). It is possible to switch OFF auto restart.
For example: after a long power failure, generators have to
start‑up. As there is limited energy and the air conditioners
do NOT have priority, it is recommended to switch OFF
auto restart.
1 Press
,
, and
simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 10.
7 Press
to confirm.
8 Press
.
9 Select 0 (0: auto restart OFF, 1: auto restart ON).
10 Press
to confirm.
5.6.5

To control cooling mode only

Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Cut the jumper J8 on the user interface of the indoor unit.
J8
2 Turn on the unit using the respective circuit breaker.
3 Turn ON the unit via the user interface.