Cooling Chart - Carrier DesertMaster 50TJM Operation And Maintenance

Package rooftop units
Table of Contents

Advertisement

Cooling Chart (cont)
140
130
120
Add charge if above upper curve
110
100
90
80
70
60
50
40
150
140
130
120
110
Add charge if above upper curve
100
90
80
70
60
50
40
150
CHARGING CHART 50TJM-28
Both Circuits
All outdoor fans must be operating
200
250
300
Fig - 12 Cooling Charging Charts for 50TJM Size 28
CHARGING CHART 50TJM-34
Both Circuits
All outdoor fans must be operating
200
250
300
Fig - 13 Cooling Charging Charts for 50TJM Size 34
Reduce charge if below lower curve
350
400
450
Liquid Pressure (PSIG)
Reduce charge if below lower curve
350
400
450
Liquid Pressure (PSIG)
Page 25
500
550
600
500
550
600