Electrical Data - Carrier DesertMaster 50TJM Operation And Maintenance

Package rooftop units
Table of Contents

Advertisement

Electrical Data Table - 3
50TJM Size 18 - 34
Unit Size
Min Voltage
50TJM
Voltage
360
360
18
360
360
360
360
24
360
360
360
360
28
360
360
360
360
34
360
360
Legend and Notes for Electrical Data Table
FLA - Full Load Amps
IFM - Indoor (Evaporator) Fan Motor
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Overcurrent Protection
* Application heater kW @ 400 volt (Using multiplication factor table in Electric Resistance Heater Data table on page 13)
Unbalanced 3-Phase Supply Voltage
Never operate a motor where phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage imbalance
Maximum Deviation From Average Voltage
= 100 X
Example: Supply Voltage is 400V - 3ph - 50Hz
AB = 392v
Average Voltage =
BC = 404v
AC = 395v
=
Determine maximum deviation from average voltage.
(AB) 397 - 392
=5v
(BC) 404 - 397
=7v
(AC) 457 - 397
=2v
Maximum Deviation is 7v.
Determine Percentage Voltage Imbalance.
% Voltage Imbalance
= 100 X
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
Compressor
Power
No.1
Max
Supply
RLA LRA RLA
V / Ph / Hz
440
400 / 3 / 50
12.2
101
440
400 / 3 / 50
12.2
101
440
400 / 3 / 50
12.2
101
440
400 / 3 / 50
12.2
101
440
400 / 3 / 50
16.7
111
440
400 / 3 / 50
16.7
111
440
400 / 3 / 50
16.7
111
440
400 / 3 / 50
16.7
111
440
400 / 3 / 50
17.9
118
440
400 / 3 / 50
17.9
118
440
400 / 3 / 50
17.9
118
440
400 / 3 / 50
17.9
118
440
400 / 3 / 50
21.8
140
440
400 / 3 / 50
21.8
140
440
400 / 3 / 50
21.8
140
440
400 / 3 / 50
21.8
140
Average Voltage
392 + 404 + 395
3
1191
= 397V
3
7
= 1.76%
397
OFM
IFM Type
No.2
LRA Qty HP FLA
12.2
101
2
1
3.4
12.2
101
2
1
3.4
High Eff.
12.2
101
2
1
3.4
12.2
101
2
1
3.4
High Eff.
16.7
111
2
1
3.4
16.7
111
2
1
3.4
High Eff.
16.7
111
2
1
3.4
16.7
111
2
1
3.4
High Eff.
17.9
118
2
1
3
17.9
118
2
1
3
High Eff.
17.9
118
2
1
3
17.9
118
2
1
3
High Eff.
21.8
140
2
1
3
21.8
140
2
1
3
High Eff.
21.8
140
2
1
3
21.8
140
2
1
3
High Eff.
NEC - National Electrical Code
OFM - Outdoor (Condenser) Fan Motor
RLA - Rated Load Amps
HACR - Heating, Air-Conditioning and Refrigeration
◊ Fuse or HACR Circuit Breaker
Page 11
Electric
IFM
Heater
Appl.
HP
FLA
KW
-
Std. Eff.
4
6.3
4
6.15
-
Std. Eff.
4
6.3
21
4
6.15
21
Std. Eff.
5.5
8.3
-
5.5
8
-
Std. Eff.
5.5
8.3
28
5.5
8
28
Std. Eff.
5.5
8.3
-
5.5
8
-
Std. Eff.
5.5
8.3
28
5.5
8
28
Std. Eff.
7.5
11.3
-
-
7.5
11
Std. Eff.
28
7.5
11.3
28
7.5
11
MCA MOCP◊
FLA
-
40.6
50
-
40.4
50
30.3
44.2
50
30.3
44.0
50
-
52.7
60
-
52.4
60
40.4
58.8
90
40.4
58.5
90
-
57.6
70
-
57.3
70
40.4
61.8
100
40.4
61.5
100
-
66.4
80
-
66.1
80
40.4
66.4
100
40.4
66.1
100