Carrier 50TFF008-014 Installation, Start-Up And Service Instructions Manual
Carrier 50TFF008-014 Installation, Start-Up And Service Instructions Manual

Carrier 50TFF008-014 Installation, Start-Up And Service Instructions Manual

Single-package rooftop cooling units
Table of Contents

Advertisement

CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33

Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
• ROOF CURB
• SLAB MOUNT
Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 1
Step 3 — Install External Trap for
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
• POSITIONING
Step 5 — Make Electrical Connections . . . . . . . . . . . 7
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 6 — Adjust Factory-Installed
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
• APOLLO CONTROL
• MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL DURABLADE ECONOMIZER
• OPTIONAL ECONOMI$ER
Step 7 — Adjust Evaporator-Fan Speed . . . . . . . . . 20
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34,35
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-38
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . 39-41
Start-Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, re-
pair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and tag. Electrical
shock could cause personal injury.
Ensure voltage listed on unit data plate agrees with electri-
cal supply provided for the unit.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 535-00010
Book 1
4
Tab
1b 6b
Single-Package Rooftop Cooling Units
Installation, Start-Up and
Service Instructions
Page
Printed in U.S.A.
50TFF008-014
INSTALLATION
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from hori-
zontal duct opening covers and remove covers. Using the same
screws, install covers on duct openings in basepan of unit with
the insulation-side down. Seals around duct openings must be
tight. See Fig. 1.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb, not to unit. If elec-
tric control power is to be routed through the basepan, attach
the accessory thru-the-bottom service connections to the roof
curb in accordance with the accessory installation instructions.
Connection must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for ad-
ditional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level
concrete slab that extends a minimum of 6 in. beyond unit cab-
inet. Install a 6-in. gravel apron in front of outdoor-coil air inlet
to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Step 2 — Field Fabricate Ductwork —
cal discharge units, secure all ducts to roof curb and building
structure. Do not connect ductwork to unit. For horizontal ap-
plications, field-supplied isolation flanges should be attached
to horizontal discharge openings and all ductwork attached to
the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be in-
sulated and covered with a vapor barrier.
If plenum return is used on a vertical unit, the return should
be ducted through the roof deck to comply with applicable fire
codes.
If electrical connections are to be routed through the
bottom of the unit, attach accessory thru-the-bottom service
connections to the basepan in accordance with installation
instructions.
Form 50TFF-2SI
Pg 1
On verti-
8-00
Replaces: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 50TFF008-014 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier 50TFF008-014

  • Page 1 50TFF008-014 Single-Package Rooftop Cooling Units Installation, Start-Up and Service Instructions CONTENTS INSTALLATION Page Unit is shipped in the vertical discharge configuration. To SAFETY CONSIDERATIONS ..... . 1 convert to horizontal configuration, remove screws from hori- INSTALLATION .
  • Page 2 Fig. 1 — Horizontal Conversion Panels Step 4 — Rig and Place Unit — A minimum clearance to combustibles is not required Inspect unit transportation damage. File any claim with transportation around ductwork on vertical discharge units. On horizontal dis- charge units, a minimum clearance of 1 in.
  • Page 3 “D” ALT CONNECTOR ROOF CURB UNIT SIZE “E” “F” “G” “A” “B” “C” DRAIN PACKAGE ACCESSORY 50TFF POWER CONTROL HOLE ACCESSORY CRRFCURB003A00 1′-2″ [356] ″ [19] NPT 008-014 ″ ″ [12.7] CRBTMPWR001A00 CRRFCURB004A00 2′-0″ [610] ″ [31.7] NPT [19] NPT CRBTMPWR002A00 ″...
  • Page 4 MAXIMUM ALLOWABLE DIFFERENCE (in.) Fig. 3 — Unit Leveling Tolerance CONDENSATE PAN (SIDE VIEW) DRAIN PLUG NOTE: Trap should be deep enough to offset maximum unit static NOTE: Drain plug is shown in factory-installed position. difference. A 4-in. trap is recommended. Fig.
  • Page 5 DURABLADE CORNER CORNER CORNER CORNER STD UNIT ECONOMI$ER ECONOMIZER WEIGHT WEIGHT WEIGHT WEIGHT “H” “J” “K” WEIGHT WEIGHT UNIT WEIGHT Ft-in. Ft-in. Ft-in. 50TFF008 1050 50TFF009 1013 1050 50TFF012 1253 50TFF014 1253 BOTTOM POWER CHART, THESE HOLES REQ’D CONNECTION SIZES FOR USE WITH ACCESSORY PACKAGES —...
  • Page 6 Table 1 — Physical Data UNIT SIZE 50TFF NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* Durablade Economizer EconoMi$er Roof Curb† COMPRESSOR Reciprocating Reciprocating Reciprocating Scroll Quantity No. Cylinders (per circuit) Oil (oz) 42 ea 65 ea 54 ea 54 ea REFRIGERANT TYPE R-22...
  • Page 7 (Such operation would invalidate any applicable Carrier warranty.) FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat...
  • Page 8 Table 2 — Electrical Data VOLTAGE COMPRESSOR ELECTRIC POWER DISCONNECT RANGE (ea) (ea) HEAT* SUPPLY SIZE† UNIT NOMINAL 50TFF V-Ph-Hz TYPE Nominal Min Max Qty Hp FLA MOCP†† kW** — — 40.1/ 40.1 45/ 45 42/ 42 7.8/10.4 21.7/ 25.0 40.1/ 40.1 45/ 45 42/ 42...
  • Page 9 Table 2 — Electrical Data (cont) VOLTAGE COMPRESSOR ELECTRIC POWER DISCONNECT RANGE (ea) (ea) HEAT* SUPPLY SIZE† UNIT NOMINAL 50TFF V-Ph-Hz TYPE Nominal Min Max Qty Hp FLA MOCP†† kW** — — 21.8 16.5 19.8 28.1 27.8 33.4 45.0 33.0 39.7 52.9 41.7...
  • Page 10 LEGEND AND NOTES FOR TABLE 2 LEGEND Determine maximum deviation from average voltage. — Full Load Amps (AB) 457 – 452 = 5 v HACR — Heating, Air Conditioning and Refrigeration (BC) 464 – 457 = 7 v — Indoor (Evaporator) Fan Motor (AC) 457 –...
  • Page 11 APOLLO CONTROL — The optional Apollo control is used to actively monitor all modes of operation as well as indoor (evaporator) fan status, filter status, and indoor-air quality. The Apollo control is designed to work with Carrier TEMP and ® systems.
  • Page 12 Assembly: FILTER 1. Determine quantity of ventilation required for building. ACCESS Record amount for use in Step 8. PANEL 2. Remove filter access panel by raising panel and swinging OUTDOOR AIR panel outward. Panel is now disengaged from track and OPENING PANEL can be removed.
  • Page 13 SCREW HOLES (TOP) HOOD HOOD SCREEN LOCATION (SCREEN SHOWN) Fig. 16 — Damper with Hood Attached Fig. 19 — Outdoor-Air Hood Details Fig. 17 — Position Setting Fig. 20 — Vertical Discharge Block-Off Plate (Sizes 012, 014 only) FILTER ACCESS 10.
  • Page 14 SHIPPING SCREW EXAMPLE: Given — Fig. 21 — Durablade Economizer Installed in Unit Negative Pressure ......0.1 in. wg Outdoor Airflow .
  • Page 15 (TERMINALS ARE UP) UNIT Fig. 28 — Durablade Economizer Barometric Relief Damper Characteristics OUTSIDE AIR SCREEN OPTIONAL ECONOMI$ER — See Fig. 29 for EconoMi$er component locations. 1. To remove the existing filter access panel, raise the panel and swing the bottom outward. The panel is now disen- gaged from the track and can be removed.
  • Page 16 3. Install the in. seal strip on the exhaust air hood top panel. Install the in. seal strip on the exhaust air hood side panels and bottom brackets. Assemble the exhaust air hood to the outdoor air opening panel as shown in Fig.
  • Page 17 ECONOMIZER CLIP UNIT FILTER HVAC UNIT RACK WIRING HARNESS ECONOMIZER UNIT BASE ECONOMIZER REAR FLANGE OUTDOOR AIR BLOCK-OFF PLATE Fig. 35 — Rear EconoMi$er Flange Installation Fig. 36 — EconoMi$er Installed in Unit LEGEND OAT — Outdoor-Air Thermostat Fig. 37 — EconoMi$er Wiring...
  • Page 18 POWER EXHAUST SYSTEM (HIGH VOLTAGE) FAN 1 FAN 2 CAPACITOR 2 CAPACITOR 1 TO FUSED DISCONNECT RELAY 2 RELAY 1 4-PIN 3-PIN GRAY RED YEL BLU GRAY CONNECTOR PLUG CONNECTOR PLUG (HIGH VOLTAGE) (LOW VOLTAGE) X2 X3 FIELD SUPPLIED WIRING SECONDARY SECONDARY 230VAC...
  • Page 19 Mechanical Cooling Lockout — Determine the outdoor-air 6. See Fig. 41 for enthalpy changeover set point. temperature at which you want the mechanical cooling (com- 7. See Fig. 42 for barometric relief damper characteristics. pressors) to be disabled. Locate the mechanical cooling lockout (MECH CLG LOCKOUT) potentiometer.
  • Page 20 Step 7 — Adjust Evaporator-Fan Speed — just evaporator-fan speed to meet jobsite requirements. Table 5 shows fan rpm at motor pulley settings, Table 6 shows motor efficiencies and Table 7 gives accessory static pressure drops. Table 8 shows motor performance. Refer to Tables 9-20 to determine fan speed settings.
  • Page 21 Table 6 — Evaporator-Fan Motor Efficiency MOTOR EFFICIENCY (%) 50TFF008-012 50TFF014 NOTE: Convert bhp to watts using the following formula: bhp (746) watts = motor efficiency Table 7 — Accessory Static/FIOP Pressure* (in. wg) 50TFF008-014 COMPONENT 2250 2500 3000 3500 4000 4500 5000...
  • Page 22 Table 7 for accessory/FIOP static pressure information. NOTES: 5. Use of a field-supplied motor may affect wire sizing. Contact 1. Boldface indicates field-supplied drive is required. your Carrier representative for details. 6. Interpolation is permissible. Do not extrapolate. indicates field-supplied motor and drive are required.
  • Page 23 NOTES: 5. Use of a field-supplied motor may affect wire sizing. Contact 1. Boldface indicates field-supplied drive is required. your Carrier representative for details. indicates field-supplied motor and drive are required. 6. Interpolation is permissible. Do not extrapolate.
  • Page 24 Table 7 for accessory/FIOP static pressure information. NOTES: 5. Use of a field-supplied motor may affect wire sizing. Contact 1. Boldface indicates field-supplied drive is required. your Carrier representative to verify. 6. Interpolation is permissible. Do not extrapolate. indicates field-supplied motor and drive are required.
  • Page 25 NOTES: 5. Use of a field-supplied motor may affect wire sizing. Contact 1. Boldface indicates field-supplied drive is required. your Carrier representative for details. indicates field-supplied motor and drive are required. 6. Interpolation is permissible. Do not extrapolate.
  • Page 26 See Table 7 for accessory/FIOP static pressure information. 4. Use of a field-supplied motor may affect wire sizing. Contact NOTES: your Carrier representative for details. 1. Boldface indicates high-static motor and drive are required. 5. Interpolation is permissible. Do not extrapolate.
  • Page 27 See Table 7 for accessory/FIOP static pressure information. 4. Use of a field-supplied motor may affect wire sizing. Contact NOTES: your Carrier representative for details. 1. Boldface indicates alternate motor and drive are required. 5. Interpolation is permissible. Do not extrapolate.
  • Page 28 Table 7 for accessory/FIOP static pressure information. 1. Boldface indicates field-supplied drive is required. 5. Use of a field-supplied motor may affect wire sizing. Contact indicates high-static motor and drive are required. your Carrier representative for details. 6. Interpolation is permissible. Do not extrapolate.
  • Page 29 Unit warranty will not be affected. See Table 8 for additional NOTES: information. 1. Boldface indicates field-supplied drive is required. 5. Use of a field-supplied motor may affect wire sizing. Contact indicates field-supplied motor and drive are required. your Carrier representative for details. 6. Interpolation is permissible. Do not extrapolate.
  • Page 30 Table 7 for accessory/FIOP static pressure information. 1. Boldface indicates field-supplied drive is required. 5. Use of a field-supplied motor may affect wire sizing. Contact indicates field-supplied motor and drive are required. your Carrier representative for details. 6. Interpolation is permissible. Do not extrapolate.
  • Page 31 Unit warranty will not be affected. See Table 8 for additional NOTES: information. 1. Boldface indicates field-supplied drive is required. 5. Use of a field-supplied motor may affect wire sizing. Contact indicates field-supplied motor and drive are required. your Carrier representative for details. 6. Interpolation is permissible. Do not extrapolate.
  • Page 32 5. Use of a field-supplied motor may affect wire sizing. Contact 1. Boldface indicates field-supplied drive is required. your Carrier representative for details. For additional information indicates high-static motor and drive are required. on motor performance, refer to Table 8.
  • Page 33 5. Use of a field-supplied motor may affect wire sizing. Contact your indicates alternate motor and drive are required. Carrier representative for details. For additional information on motor performance, refer to Table 8. 6. Interpolation is permissible. Do not extrapolate.
  • Page 34 START-UP temperature shuts unit off temporarily until space temperature exceeds thermostat setting. Unit Preparation — Make sure that unit has been in- Heating (If Accessory Electric Heater is stalled in accordance with these installation instructions and Installed) — applicable codes. Ensure Start-Up Checklist on back page of To start unit, turn on main power supply.
  • Page 35 When the second stage of cooling is satisfied, the compres- SERVICE sor and condenser-fan motors will be deenergized. The damper position will be determined by the supply-air temperature. When the first stage of cooling is satisfied and the indoor When servicing unit, shut off all electrical power to unit to (evaporator) fan motor is deenergized, the damper will move to avoid shock hazard or injury from rotating parts.
  • Page 36 inspections or as conditions require. Replace belt or adjust as necessary. Refer to Step 7 — Adjust Evaporator-Fan Speed on page 20 for proper adjustment procedures and belt tension. Condenser-Fan Adjustment (Fig. 49) 1. Shut off unit power supply, tag disconnect. 2.
  • Page 37 2. Using hoses with valve core depressors, attach low- and Loss-of-Charge Switch — Located on the condenser high-pressure gage hoses to low- and high-pressure ser- liquid line is a low-pressure switch which functions as a loss- vice fittings, respectively. of-charge switch. This switch contains a Schrader core depres- sor.
  • Page 38 CIRCUIT NO. 2 CIRCUIT NO. 1 Fig. 52 — Cooling Charging Chart; 50TFF012 Fig. 53 — Cooling Charging Chart; 50TFF014...
  • Page 39: Troubleshooting

    TROUBLESHOOTING Tables 21-23 are provided for troubleshooting the unit and economizer. Table 21 — Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and Power failure. Call power company. condenser fans Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. will not start.
  • Page 40 Table 22 — Durablade Economizer Service Analysis PROBLEM CAUSE REMEDY Damper does not Indoor (evaporator) fan is off. 1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that open. 24 vac is present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire).
  • Page 41 Table 23 — EconoMi$er Service Analysis PROBLEM CAUSE REMEDY Damper does Indoor (evaporator) Check to ensure that 24 vac is present at Terminal C1 (common power) on the IFC not open. fan is off. (indoor [evaporator] fan contactor) or that 24 vac is present at the IFO (indoor [evaporator] fan on) terminal.
  • Page 42 Copyright 2000 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 535-00010 Printed in U.S.A. Form 50TFF-2SI Pg 42 8-00 Replaces: New...
  • Page 44 VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGES 37-38 (COOLING MODE ONLY) VERIFY 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION Copyright 2000 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book PC 111 Catalog No.

Table of Contents

Save PDF