Carrier 50TJ016-028 Installation, Start-Up And Service Instructions Manual

Single-package rooftop units 50 hz

Advertisement

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Step 1 - Provide Unit Support . . . . . . . . . . . . . . . 1
• ALTERNATE UNIT SUPPORT
Step 2 - Rig and Place Unit . . . . . . . . . . . . . . . . . . 1
• POSITIONING
• ROOF MOUNT
Step 3 - Field Fabricate Ductwork . . . . . . . . . . . . 8
Step 5 - Trap Condensate Drain . . . . . . . . . . . . . 8
• FIELD CONTROL WIRING
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL ECONOMIZER
Step 8 - Install Outdoor-Air Hood . . . . . . . . . . . 11
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-17
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-22
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical com-
ponents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, ob-
serve precautions in the literature, tags and labels attached
to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire ex-
tinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Catalog No. 005-072
Tab
1b
Installation, Start-Up and
Service Instructions
Page
Printed in U.S.A.
Single-Package Rooftop Units
INSTALLATION
Step 1 - Provide Unit Support
ROOF CURB - Assemble and install accessory roof curb
or horizontal adapter in accordance with instructions shipped
with the curb or adapter. Accessory roof curb and horizontal
adapter and information required to field fabricate a roof curb
or horizontal adapter are shown in Fig. 1. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work can be secured to roof curb or horizontal adapter be-
fore unit is set in place.
IMPORTANT: The gasketing of the unit to the roof
curb or horizontal adapter is critical for a watertight
seal. Install gasket supplied with the roof curb or hori-
zontal adapter as shown in Fig. 1. Improperly applied
gasket can result in air leaks and poor unit
performance.
Curb or adapter should be level. This is necessary to per-
mit unit drain to function properly. Unit leveling tolerance is
± 5 mm per linear m (±
Refer to Accessory Roof Curb or Horizontal Adapter Instal-
lation Instructions for additional information as required.
ALTERNATE UNIT SUPPORT - When the curb or adapter
cannot be used, support unit with sleepers using unit curb or
adapter support area. If sleepers cannot be used, support long
sides of unit with a minimum of 3 equally-spaced 100 mm
× 100 mm (4 in. × 4 in.) pads on each side.
Step 2 - Rig and Place Unit -
portation damage. File any claim with transportation agency.
Keep unit upright, and do not drop. Use bumper boards for
spreader bars over unit to prevent sling or cable damage.
Rollers may be used to move unit across a roof. Level by
using unit frame as a reference; leveling tolerance is ± 5 mm
per linear m (±
1
in. per linear ft) in any direction. See
16
Fig. 2 for additional information. Unit weight is shown in
Tables 1A and 1B.
Four lifting holes are provided in ends of unit base rails
as shown in Fig. 2-4. Refer to rigging instructions on unit.
POSITIONING - Provide clearance around and above unit
for airflow, safety, and service access (Fig. 3 and 4).
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
ROOF MOUNT - Check building codes for weight distri-
bution requirements.
Form 50TJ-C8SI
Pg 1
50TJ016-028
50 Hz
1
in. per linear ft) in any direction.
16
Inspect unit for trans-
5-96
Replaces: 50TJ-C4SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 50TJ016-028

  • Page 1: Table Of Contents

    50TJ016-028 Single-Package Rooftop Units 50 Hz Installation, Start-Up and Service Instructions INSTALLATION CONTENTS Step 1 — Provide Unit Support Page ROOF CURB — Assemble and install accessory roof curb SAFETY CONSIDERATIONS ....1 or horizontal adapter in accordance with instructions shipped INSTALLATION .
  • Page 2: Installation

    NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor-air section, unit can only be pitched as shown. LEGEND COMP SECT. — Compressor Section NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels, 13 mm ( ⁄...
  • Page 3 DIMENSIONS MAXIMUM UNIT SHIPPING WEIGHT 50TJ Ft-in. Ft-in. 2150 6-11 ⁄ 2121 1219 2700 1225 6-11 ⁄ 2121 1092 2750 1247 6-11 ⁄ 2121 1041 NOTES: 1. Dimensions in ( ) are in millimeters. 2. Refer to Tables 1A and 1B for unit operating weights. 3.
  • Page 4 LEGEND KO — Knockout CONDENSATE DRAIN PIPING NOTES: 1. Dimensions in ( ) are in millimeters. Center of gravity. Direction of airflow. 4. Ductwork to be attached to accessory roof curb only. 5. Minimum clearance: a. Rear: 7 -0 (2134) for coil removal. This dimen- sion can be reduced to 4 -0 (1219) if conditions permit coil removal from the top.
  • Page 5 CONDENSATE DRAIN PIPING LEGEND KO — Knockout NOTES: 1. Dimensions in ( ) are in millimeters. Center of gravity. Direction of airflow. 4. Ductwork to be attached to accessory roof curb only. 5. Minimum clearance: a. Rear: 7 -0 (2134) for coil removal. This di- mension can be reduced to 4 -0 (1219) if conditions permit coil removal from the top.
  • Page 6: Roof Curb

    Table 1A — Physical Data, 50TJ016-028 (SI) UNIT SIZE NOMINAL CAPACITY (kW) 52.8 70.3 87.9 OPERATING WEIGHT (kg) Unit Al/Al* Al/Cu* 1021 1043 Economizer Roof Curb† Electric Heat COMPRESSOR Semi-Hermetic Quantity No. Cylinders Oil (ml) 3401 3781 ea 3781 ea...
  • Page 7 Table 1B — Physical Data, 50TJ016-028 (English) UNIT SIZE NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* 1550 2100 2150 Al/Cu* 1700 2250 2300 Economizer Roof Curb† Electric Heat COMPRESSOR Semi-Hermetic Quantity No. Cylinders Oil (oz) 128 ea 128 ea...
  • Page 8: Step 3 - Field Fabricate Ductwork

    Step 3 — Field Fabricate Ductwork — Secure all ducts to building structure. Use flexible duct connectors be- tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
  • Page 9: Field Control Wiring

    Unit failure as a result of operation on improper line volt- age or excessive phase imbalance constitutes abuse and may cause damage to electrical components. FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.
  • Page 10: Step 7 - Make Outdoor-Air Inlet

    Table 2 — Electrical Data, 50TJ016-028 COMPRESSOR VOLTAGE ELECTRIC POWER SUPPLY NOMINAL RANGE HEAT* UNIT No. 1 No. 2 VOLTAGE 50TJ Nominal (3 Ph, 50 Hz) Quantity MOCP** (ea) — — 29.0 — — 58† — — 19.9 19.9 ⁄...
  • Page 11: Step 8 - Install Outdoor-Air Hood

    Step 8 — Install Outdoor-Air Hood — The same type of factory-installed hood is used on units with 25% air ventilation and units with an economizer. NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baffle (028 units), and filter support bracket are secured opposite the condenser end of the unit.
  • Page 12 Refrigerant Service Ports — Each refrigerant sys- tem has one service port located in the top of the compressor motor casing. All units also have one service port on the liq- uid line and one on either the discharge flange or the dis- charge line.
  • Page 13 — — — — LEGEND 5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. BkW — Fan Input kW × Motor Efficiency 6. To convert kilowatts to bkW: — Kilowatt Input to Motor BkW = kW ×...
  • Page 14 — — — — — 5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier LEGEND representative to verify. BkW — Fan Input kW × Motor Efficiency 6. To convert kilowatts to bkW: — Kilowatt Input to Motor BkW = kW ×...
  • Page 15 Table 10 — Fan Performance Data (English) — 50TJ024 EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts 6,000 1428 1723 2025 2339 1041 2669...
  • Page 16 Table 12A — Accessory/FIOP Static Pressure (Pa) — 50TJ016 COMPONENT 2125 2360 2831 3400 3525 Economizer Glycol Coil Electric Heat (kW) LEGEND NOTES: 1. The static pressure must be added to external static pressure. The FIOP — Factory-Installed Option sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
  • Page 17 Table 14A — Fan R/s at Motor Pulley Settings (SI) MOTOR PULLEY TURNS OPEN UNIT 50TJ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ 22.47 22.05 21.62 21.20 20.77 20.35 19.93 19.50 19.08 18.65 18.23 — — 024,028 23.40 23.07 22.76 22.44 22.12 21.81 21.50...
  • Page 18: Service

    have grease fittings. The bearing opposite the motor end has SERVICE an extended tube line so it can be lubricated from the motor side. Lubricate the bearings twice annually. Typical lubricants are given below: Before performing service or maintenance operations on unit, turn off main power switch to unit.
  • Page 19: Service

    50TJ024,028 UNITS (See Fig. 24) — The 50TJ024,028 units use a fan motor mounting system that features a slide-out motor mounting plate. To replace or service the motor, slide out the bracket. 1. Remove the evaporator-fan access panel and the heat- ing control access panel.
  • Page 20 4. Adjust bolts and nut on mounting plate to secure motor is listed on unit nameplate and in Tables 1A and 1B. Refer in fixed position. to Carrier GTAC II; Module 5; Charging, Recovery, Recy- cling, and Reclamation section for charging methods and Condenser-Fan Adjustment procedures.
  • Page 21 NO CHARGE — Use standard evacuating techniques. After EVAPORATOR-FAN MOTOR PROTECTION — A manual evacuating system, weigh in the specified amount of refrig- reset, calibrated trip, magnetic circuit breaker protects against erant (refer to Tables 1A and 1B). overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble.
  • Page 22: Book 1 Catalog No. 005-072 Printed In U.s.a

    If it trips, determine cause of trouble before resetting. Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request. Fig. 29 — Cooling Charging Chart, 50TJ028 Fig. 28 — Cooling Charging Chart, 50TJ024 Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
  • Page 24: Start-Up Checklist

    VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 21 AND 22. GENERAL ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 Catalog No.

Table of Contents