Table 27 - Error Code; Troubleshooting - Honeywell 2MLF-HO2A User Manual

High speed counter module
Table of Contents

Advertisement

8.1
Error Code
This chapter describes the process of diagnosing and solving the errors of High Speed
Counter module.
Errors of High Speed counter module are described below.
Error code
(Dec)
CH0
CH1
10
Module error (ASIC Reset error)
11
Module error (ASIC RAM error)
12
Module error (ASIC Register error)
20
120
Counter type range exceeded
21
121
Pulse input type range exceeded
22
122
Auxiliary Mode type range exceeded
23
123
Sampling Count value range exceeded
24
124
Compared output0 type range exceeded
25
125
Compared output1 type range exceeded
26
126
Preset value exceeded counter range
Ring counter minimum value ≥ Ring counter maximum value
27
127
input
Compared output 0 minimum value exceeded maximum input
28
128
range
Compared output 0 maximum value exceeded maximum input
29
129
range
Compared output 0 minimum value > compared output 0
30
130
maximum value set
Compared output 1 minimum value exceeded maximum input
31
131
range
R200
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
May 2010

8. Troubleshooting

Table 27 – Error Code
Description
Honeywell
RUN LED
status
Blinks every 0.2
sec.
Blinks every 1
sec