Commercial Condensing Gas-Fired Water Boiler — Boiler Manual
Maintenance
Figure 103
Heat exchanger cover plate gasket and cover plate
re-installation
Heat exchanger
cover plate gasket
4. Allow time for the burner or cover plate insulation to dry completely
if they do get wet.
Inspect burner access plate / burner gasket
Inspect the silicone burner access plate gasket and graphite burner gasket.
Replace if damaged.
Burner Access Method (re-install)
Follow the procedure on page 97 (steps 12-16) to re-install the burner and
access plate to the heat exchanger.
Hinged Cover Plate Method (re-install)
1. Push down on the top of the blower to allow the locking pin to be
removed.
2. Slowly and steadily lower the cover plate, ensuring the gasket lands
properly in the gasket groove on the heat exchanger.
3. Gradually tighten the 12 bolts securing the cover plate to the heat
exchanger in the order shown on Figure 104, page 110 to a torque of
15 ft .-lbs.
4. Re-install locking pin into cover plate storage location.
5. Install the gas manifold.
a. Install the four (4) M5 screws securing the gas manifold to the
blower swirl plate. Ensure the O-ring is seated properly and not
damaged.
b. Install the four (4) M8 screws securing the gas manifold to the
automatic gas valve. Ensure the O-ring is seated properly and not
damaged.
6. Install the air inlet fi lter and slide support bracket up until it makes
contact with the rubber end of the air fi lter. Tighten the two (2) screws
to secure it.
7. Insert the reference tube into the air inlet shroud.
8. Install the front left and right side panels.
Part number 550-100-250/0819
(continued)
Burner
9. Swing the top rear panel support brackets back into posi-
tion. Secure screws with a 5/16 nut driver.
10. Install the top rear and middle panels.
Burner gasket and burner access gasket
If the burner or burner access plate gaskets
have been damaged or stretched, replace the
damaged or stretched gasket before placing the
boiler back in operation.
Filter Condition
1. A dirty or blocked fi lter will reduce boiler effi ciency. A
fi lter condition gauge is present with each boiler. Inspect
the fi lter gauge regularly.
2. If the fi lter gauge marker is in the red zone, the fi lter needs
to be cleaned or replaced.
3. Clean the fi lter using compressed air. Remove the fi lter by
loosening the hose clamp with a 5/16" nutdriver. From the
inside, blow out the fi lter along each of pleats until no more
dust or debris is blown out.
4. Aft er replacing the fi lter, reset the fi lter gauge by pressing
the yellow reset butt on.
5. If the fi lter gauge marker remains in the green zone, no fi lter
cleaning or replacement is necessary.
Restart and test the boiler
1. Restore gas supply and power to the boiler.
2. Start the boiler and verify operation following the proce-
dures given in this manual.
Failure to follow the provided procedures could
result in a gas/air or exhaust gasses leak which
can cause severe personal injury, death or sub-
stantial property damage.
109