Weil-McLain SVF 1500 Manual page 104

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SVF 1500:
Table of Contents

Advertisement

SVF
Series 1
Commercial Condensing Gas-Fired Water Boiler — Boiler Manual
Troubleshooting
Figure 102 Troubleshooting suggestions for
Control Fault Displays, Diagnostics and Suggested Corrective Actions
Display
Condition
LOW WTR
Occurs if internal low water
CUTOFF OPEN
cutoff contacts open.
Boiler Out temperature
SUPPLY 58° F >
has exceeded the Boiler In
RETURN
temperature by more than
58º F.
RETURN >
Occurs if a return water
SUPPLY
temperature is greater than
the corresponding supply
temperature by 10º F or more.
SUPPLY WATER
Occurs when the System
Supply temperature goes
TEMPERATURE
above 200º F when the
TOO HIGH
burner is running.
TEMPERATURE
Occurs if a temperature
SENSOR FAULT
sensor has electrically shorted
(SHORT) or has become
disconnected (OPEN).
104
(continued)
TM
SVF
boilers
(continued)
Diagnostics
Automatic reset occurs if
contacts are open at least one
second, but less than 5 seconds.
Manual reset of control if
contacts are open longer than
5 seconds.
Automatically resets after 2
minutes 30 second delay when
conditions no longer exists.
If the burner has been on
for less than 2 minutes the
condition occurs:
1st time: 2 min 30 sec
2nd time: 3 min 30 sec
3rd time: 4 min 30 sec
4th time: 5 min 30 sec
5th time: 6 min 30 sec and every
time after
* timer resets once the burner
is able to run longer than 2
minutes.
Automatically resets when
condition no longer exists.
Automatically resets when
Supply temperature goes below
200º F.
Will automatically reset if the
condition clears.
Corrective Action(s)
Check for low water condition in system. Repair system as necessary
refer to piping section of this manual.
If low water condition does not exist, check Diagnostics — Inputs screen
to view status of Low Water Cutoff. If shown as OPEN check wiring
between LWCO and control. If wiring is all right, remove LWCO and Clean
probe. If problem still exist, then replace the LWCO.
Low water cutoff indicator light codes:
GREEN on = Normal operation
RED on = LWCO open / Low water condition
Verify water pipe is installed correctly per instructions in this manual.
Verify proper circulator and speed for boiler size and system
requirements.
See message displayed TEMPERATURE SENSOR and follow procedure for
loose connections.
Verify proper flow direction of the boiler circulator.
Verify proper placement of system sensors for single or multiple boiler
system. System sensors should be on system piping not on the boiler
loop.
Verify sensors are wired to correct terminal locations.
System sensors may need to be located further away from the boiler
loop connection to the system, if proximity to the boiler loop is causing
sensors to be heated inaccurately.
Verify proper flow direction of the boiler circulator. This circulator must be
installed to push water through the system.
Check all the temperature readings of the boiler on the DIAGNOSTICS -
TEMPERATURES menu to determine if any sensors are currently displayed
as SHORT or OPEN. Compare this to the boiler temperatures recorded
in the DIAGNOSTICS - ERRORS - LOCKOUT HISTORY # - TEMPERATURES
during the last several lockout conditions.
Determine which sensors are suspect and measure their resistance
value and compare it to the values shown in Figure 94, page 98. If the
resistance values are incorrect replace the temperature sensor. Refer to
repair parts section for proper part number.
Check wire harness for loose connections and pin engagement at sensor
connection, chassis mount connection through control housing, and
the control. Unplug connection at sensor and at control and check
continuity between ends.
If problem persists after checking items above, replace control. Refer to
repair parts section for kit number.
Part number 550-100-250/0819

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Svf 3000Svf 2000Svf 1 seriesSvf 2500

Table of Contents