14.14 Analog output

Whether the analog output is available or not, depends on the
functional module fitted in the pump:
Function (terminal)
Analog output
* See section
22. Identifying the functional
The analog output enables the transfer of certain operating data
to external control systems.
To set the analog output, make the settings below.
Output signal
0-10 V
0-20 mA
4-20 mA.
Function of analog output
Actual speed
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
the reading is a percentage of nominal speed.
Actual value
Signal range
[V, mA]
Sensor
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the range between sensor
sensor
.
max
Resulting setpoint
Signal range
[V, mA]
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the external setpoint range.
FM 200*
FM 300*
(standard)
(advanced)
-
module.
Actual speed
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
Actual value
Sensor
min
max
10 V
20 mA
20 mA
and
min
Resulting setpoint
[%]
0
100
10 V
20 mA
20 mA
Motor load
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
Reading is a percentage of the range between 0 and 200 % of the
maximum permissible load at the actual speed.
Motor current
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the range between 0 % and 200 %
of the rated current (I
).
N
Limit 1 exceeded and Limit 2 exceeded
This function is only available on TPE2, TPE2 D pumps.
Limit-exceeded function
Signal range
[V, mA]
Output not active
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
Limit-exceeded function is typically used for monitoring of
secondary parameters in the system. If the limit is exceeded, an
output, warning or alarm is activated.
Flow rate
Signal range
[V, mA]
0
0-10 V
0 V
0-20 mA
0 mA
4-20 mA
4 mA
The reading is a percentage of the range between 0 and 200 % of
the nominal flow (Q
).
nom
Factory setting
See section
31. Factory
settings.
Motor load
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
Motor current
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
Output active
10 V
20 mA
20 mA
Flow rate
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
37