Grundfos TPE 2 Series Installation And Operating Instructions Manual page 11

Table of Contents

Advertisement

OC
DI
+24 V*
+24 V*
+24 V*/5 V*
+24 V*
OC
+24 V*
GND
+24 V*
+24 V*
+24 V*/5 V*
+
+24 V*
+24 V*
+24 V*/5 V*
* If you use an external supply source, there must be a
connection to earth.
Fig. 19 Connection terminals, FM 300 (option)
NC
C1
NO
NC
C2
NO
18
GND
11
DI4/OC2
19
Pt100/1000
17
Pt100/1000
12
AO
GND
9
+5 V*
14
AI3
1
DI2
21
LiqTec
20
GND
22
LiqTec
DI
10
DI3/OC1
4
AI1
2
DI1
+
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
+5 V*
7
AI2
Terminal
Type
Normally closed
NC
contact
C1
Common
Normally open
NO
contact
Normally closed
NC
contact
C2
Common
Normally open
NO
contact
18
GND
11
DI4/OC2
19
Pt100/1000 input 2
17
Pt100/1000 input 1
12
AO
9
GND
14
AI3
1
DI2
21
LiqTec sensor input 1
20
GND
22
LiqTec sensor input 2
10
DI3/OC1
4
AI1
2
DI1
5
+5 V
6
GND
A
GENIbus, A
Y
GENIbus, Y
B
GENIbus, B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
7
AI2
Function
Signal relay 1
LIVE or SELV
Signal relay 2
SELV only
Earth
Digital input or output,
configurable.
Open collector: Max. 24 V
resistive or inductive.
Pt100/1000 sensor input
Pt100/1000 sensor input
Analog output:
0-20 mA / 4-20 mA
0-10 V
Earth
Analog input:
0-20 mA / 4-20 mA
0-10 V
Digital input, configurable
LiqTec sensor input (white
conductor)
Earth
(brown and black
conductors)
LiqTec sensor input (blue
conductor)
Digital input or output,
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
Digital input, configurable
Supply to potentiometer
and sensor
Earth
GENIbus, A (+)
GENIbus, GND
GENIbus, B (-)
Earth
Supply
Supply
Supply to potentiometer
and sensor
Earth
Grundfos Digital Sensor
output
Grundfos Digital Sensor
input
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpe 3 seriesTpe3Tpe3 dTpe2Tpe2 d

Table of Contents