Grundfos TPE 2 Series Installation And Operating Instructions Manual page 41

Table of Contents

Advertisement

"Inverse with Stop" and "Inverse with Min."
– Inverse with Stop
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Stop".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal". See fig. 64.
– Inverse with Min.
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal". See fig. 64.
Setpoint influence [%]
100
0
0
0.5
0
0
0
4
-50
Normal
Min. or
Stop
Fig. 64 "Inverse with Stop" and "Inverse with Min."
Influence table
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
Setpoint influence [%]
100
0
0
0.5
0
0
0
4
-50
Fig. 65 Influence table, example with five points
External
80
100 %
input
3.5 V
5 V
10 V
20 mA
20 mA
204 C
External
100 %
input
3.5 V
5 V
10 V
20 mA
20 mA
204 C
Influence table with Stop at Min.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point. If
the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal". See fig. 66.
Setpoint influence [%]
100
0
0
20
0.5
0
0
0
4
-50
Normal
Min. or
Stop
Fig. 66 Influence table with Stop at Min., example with five
points
Influence table with Stop at Max.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point. If
the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating mode
will be changed back to "Normal". See fig. 67.
Setpoint influence [%]
100
0
0
0.5
0
0
0
4
-50
Normal
Min. or
Stop
Fig. 67 Influence table with Stop at Max., example with five
points
External
100 %
input
3.5 V
5 V
10 V
20 mA
20 mA
204 C
External
80
100 %
input
3.5 V
5 V
10 V
20 mA
20 mA
204 C
41