8 - HEAT RECLAIM CONDENSER OPTION (OPTION 50)

8.3 - Condenser location

The heat reclaim condenser is located between the air-cooled
condensers on the upper part of the chassis, support-ed by two 
cross rails. The water inlet and outlet are on the same side.

8.4 - Condenser water connections

8.4.1 - Connection diagram
The water flow switch must be installed at the water inlet of the 
installation that arrives at the heat reclaim condenser.
Legend
1
Heat reclaim condenser
2
Entering water temperature sensor (supplied)
3
Leaving water temperature sensor (supplied)
4 
Condenser water flow switch (supplied)
5
Three-way valve (not supplied)
8.4.2 - Three-way valves
It is strongly recommended to install a three-way valve in the
system (not supplied with the unit). A 0-10 V output is available
on the unit electronic board to control this valve. The valve allows
bypassing of the heat reclaim condenser entering/leaving circuit 
to ensure unit operation with heat reclaim at low entering water
temperature (< 12.5 °C). It also ensures an optimal and controlled
leaving water temperature.
8.5 - Operating limits for stable operation (no
mode changeover)
8.5.1 - Cooling only mode
Please refer to the earlier chapters in this manual:
- Unit operating range
- Evaporator water flow rate
8.5.2 - Heat reclaim mode
Condenser water temperature, °C
Water entering temperature at start-up
Water entering temperature during operation
Water leaving temperature during operation
Evaporator water temperature, °C
Water entering temperature at start-up
Water entering temperature during operation
Water leaving temperature during operation
(1) The water entering temperature at start-up must not be lower than 12.5 °C.
For installations with a lower temperature a three-way valve must be used.
NOTE: If the temperature at the evaporator is below 4 °C, a glycol/water solution or 
the frost protection option must be used.
In  part-load  operation,  the  limitation  of  the  condenser  leaving 
water temperature is due to the operating range of the screw
compressor. If the condenser leaving water temperature is above
the limit value given in the curves below, the unit will automatically 
change over to the mode without heat recovery:
26
Part load operating limits (evaporator leaving water
8.6 - Operating limits for changeover between
modes
From cooling only to heat reclaim and vice versa.
Heat reclaim condenser water temperature, °C Minimum Maximum
Water entering temperature
Minimum Maximum
Ambient operating temperature
12,5
55
(1)
20
55
(1) -20 °C with winter operation option (option 28)
25
60
Minimum Maximum
-
45
6,8
21
3,3
15
6 5
6 0
5 5
5 0
4 5
4 0
3 5
3 0
2 5
2 0
0
5
Evaporator leaving water temperature, °C
Full load
Part load limit, approx. 60%
Minimum load limit, approx. 30%
temperature = 7 °C)
60
55
50
45
40
100
90
80
70
Unit load, %
1 0
1 5
60
50
40
30
12,5
57,5
-10
45
(1)