Variable Flow Evaporator; System Minimum Water Volume; Maximum System Water Volume; Evaporator Water Flow Rate - Carrier Aquaforce 30XAS Series Installation, Operation And Maintenance Instructions

Air-cooled liquid chillers. nominal cooling capacity: 232-486 kw - 50 hz
Hide thumbs Also See for Aquaforce 30XAS Series:
Table of Contents

Advertisement

6 - APPLICATION DATA

6.4 - Variable flow evaporator

Variable evaporator flow can be used in standard 30XAS chillers. 
The chillers maintain a constant leaving water tem-perature under
all flow conditions. For this to happen, the minimum flow rate must 
be higher than the minimum flow given in the table of permissible 
flow rates and must not vary by more than 10% per minute.
If the flow rate changes more rapidly, the system should contain 
a minimum of 6.5 litres of water per kW instead of 3.25 l/kW.

6.5 - System minimum water volume

Whichever the system, the water loop minimum capacity is given 
by the formula:
Capacity = Cap (kW) x N litres
Application
Normal air conditioning
Process type cooling
Where Cap is the nominal system cooling capacity (kW) at the
nominal operating conditions of the installation.
This volume is necessary for stable operation and accurate
temperature control.
It is often necessary to add a buffer water tank to the circuit in
order to achieve the required volume. The tank must itself be
internally  baffled  in  order  to  ensure  proper  mixing  of  the  liquid 
(water or brine). Refer to the examples below.
Connection to a buffer tank
Bad
Bad
N
3,25
6,5
Good
Good

6.6 - Maximum system water volume

Units with hydraulic module incorporate an expansion tank that
limits the water volume. The table below gives the maximum loop
volume for pure water or ethylene glycol with various system
concentrations, as well as the static pressures. If the maximum 
volume  is  insufficient,  compared  to  the  minimum  system  water 
loop volume, an additional expansion tank must be added to the 
system.
30XAS
Static pressure
Maximum water loop volume
Pure water
Ethylene glycol 10%
Ethylene glycol 20%
Ethylene glycol 30%
Ethylene glycol 40%

6.7 - Evaporator water flow rate

Evaporator water flow rate, l/s
30XAS
Min, flow rate
242
3,2
282
3,7
342
4,4
442
5,8
482
6,5
(1)  The maximum water flow rate corresponds to a pressure drop of 100 kPa.

6.8 - Evaporator pressure drop curve

Legend
1
30XAS 242-342
2
30XAS 442-482
242-482
bar
1
l
2400
1800
1320
1080
900
Max, flow rate
30,7
30,7
30,7
41,0
41,0
Water flow rate, l/s
2
1600
1200
880
720
600
(1)
19