9.4 - Variable flow evaporator

Variable evaporator flow can be used in standard 30HXC and
30GX chillers. The chillers maintain a constant leaving water
temperature under all flow conditions. For this to happen, the
minimum flow rate must be higher than the minimum flow
given in the table of permissible flow rates and must not vary
by more than 10% per minute. If the flow rate changes more
rapidly, the system should contain a minimum of 6.5 liters of
water per kW instead of 3.25 l/kW.

9.5 - System minimum water volume

Whichever the system, the water loop minimum capacity is
given by the formula:
Capacity = Cap (kW) x N Liters
Application
Normal air conditioning
Process type cooling
Where Cap is the nominal system cooling capacity (kW) at the
nominal operating conditions of the installation.
This volume is necessary for stable operation and accurate
temperature control.
It is often necessary to add a buffer water tank to the circuit in
order to achieve the required volume. The tank must itself be
internally baffled in order to ensure proper mixing of the liquid
(water or brine). Refer to the examples below.
NOTE: The compressor must not restart more than 6 times in
an hour.
GOOD
BAD
14
N
3.25
6.5
BAD
GOOD

9.6 - Cooler flow rate (l/s)

30HXC
Min.*
080-090
100
110
120-130
140-155
10.0
175-190
10.7
200
13.4
230
13.4
260-285
17.0
310
19.4
345-375
21.3
30GX
Min.*
082
092-102
112-122
132
152-162
10.0
182
10.7
207-227
13.4
247
15.1
267
17.0
298
19.4
328-358
21.3
* Based on a water velocity of 0.9 m/s.
** Based on a water velocity of 3.6 m/s.

9.7 - Condenser flow rate (l/s)

30HXC
Min.*
Closed
loop
080-110
2.5
120-130
3.1
140-155
3.8
175-190
4.6
200
5.0
230-285
6.7
310-375
7.3
* Based on a water velocity of 0.3 m/s in a closed loop and 0.9 m/s in an open
loop.
** Based on a water velocity of 3.6 m/s.
Max.**
5.7
22.7
6.0
24.1
6.9
27.5
8.3
33.0
39.5
42.7
53.7
60.6
68.1
77.8
85.3
Max.**
5.7
22.7
6.0
24.1
6.9
27.5
8.4
33.7
39.9
42.7
53.7
60.6
68.1
77.8
85.3
Max.**
Open
loop
7.5
29.9
9.3
37.3
11.4
45.5
13.8
55.2
14.9
59.6
20.1
80.3
22.0
88.0