Settings Of Connection Using Fp0H As Target; Settings - Panasonic AFP0HC32ET User Manual

Ethernet/ip programmable controller
Table of Contents

Advertisement

Setting Procedure

3.4 Settings of Connection Using FP0H as Target

3.4.1 Settings

This section describes the setting method of the connection using the FP0H as target,
The FP0H(A) in the figure below is an object for the setting.
Ten word data is sent from the data area (LD30 to 39) of the FP0H(A) to the data area (LD30
to 39) of FP7.
Originator
Target
• When the FP0H is used as target, only the data transmission to originator is available.
• Register a tag (Tag_Test1) specified from the FP7 (Originator) in the "I/O map".
• Set the data area (LD30 to 39) corresponding to the tag.
3-16
FP7
IP:192.168.1.5
FP0H(A)
IP:192.168.1.6
Tag_Test1
LD30
LD39
Tag_Test1
LD30
LD39
LD40
LD49
Set in I/O map.