Electrical Power Network Specification; Motor Connection Data; Control Unit Connection Data; Efficiency - ABB ACS580-07 Hardware Manual

Hide thumbs Also See for ACS580-07:
Table of Contents

Advertisement

Electrical power network specification

Voltage (U
)
1
Network type
Short-circuit withstand
strength (IEC 61439-1)
Short-circuit current
protection (UL 508C)
Frequency (f
)
1
Imbalance
Fundamental power
factor (cos phi
)
1

Motor connection data

Motor types
Voltage (U
)
2
Frequency (f
)
2
Current
Switching frequency
Maximum recommended
motor cable length

Control unit connection data

See chapter
Control unit (page

Efficiency

Approximately 98% at nominal power level
ACS580-07-xxxxx-4 drives: 380...480 VAC 3-phase ±10%. This is indicated in the
type designation label as typical input voltage levels 3~400/480 V AC.
TN (grounded) and IT (ungrounded) systems
Maximum allowable prospective short-circuit current is 65 kA when the input cable
is protected with gG type fuses (IEC 60269) having maximum operating time of
0.1 seconds and maximum current rating:
• 400 A for frames R6 to R8
• 630 A for frame R9
• 1000 A for R10
• 1250 A for R11
The drive is suitable for use on a circuit capable of delivering not more than 100,000
rms symmetrical amperes at 480 V maximum when the input cable is protected
with UL class T or L fuses. For selection of fuses for branch circuit protection, see
section
Fuses for branch circuit protection (page
faster are recommended in the USA. Obey local regulations.
50/60 Hz. Variation ±5% of nominal frequency.
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
Asynchronous AC induction motors, permanent magnet synchronous motors
0 to U
, 3-phase symmetrical. This is indicated in the type designation label as
1
typical output voltage level 3 ~ 0...U
0...500 Hz
For drives with du/dt filter: 500 Hz
See section
Ratings (page
3 kHz (typically)
300 m (984 ft).
Longer cables cause a motor voltage decrease which limits the available motor
power. The decrease depends on the motor cable length and characteristics. Note
that a sine filter (optional) at the drive output also causes a voltage decrease.
Contact ABB for more information.
Note:
With motor cables longer than 100 m (328 ft), the EMC Directive requirements
may not be fulfilled.
115).
178). Fast acting class T and L or
. U
at the field weakening point.
1
max
171).
Technical data 211