Start-up

Contents of this chapter

This chapter contains the start-up procedure of the drive. The default device designations
(if any) are given in brackets after the name, for example "main switch-disconnector (Q1)".
The same device designations are also used in the circuit diagrams, typically.

Start-up procedure

Action
Safety
WARNING!
Obey the safety instructions during the start-up procedure. See chapter
tions (page
15).
Checks/Settings with no voltage connected
Check the mechanical and electrical installation of the drive. See
drive (page
129).
Powering up the drive
Close the cabinet doors.
Make sure that it is safe to connect voltage. Ensure that:
• cabinet doors are closed
• nobody is working on the drive or circuits that have been wired from outside into the drive cabinet
• cover of the motor terminal box is on.
Close the main switch-disconnector (Q1).
Setting up the drive parameters, and performing the first start
9
Safety instruc-
Installation checklist of the
Start-up 131
12