Upload Segment - Danfoss FC 300 Manual

Canopen
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 CANopen

Upload segment

The upload segment command is used when more than 5 bytes will be uploaded.
Client request:
0 Byte
7..5 ccs
4 t
3..0 X
Server response:
0 Byte
7..5 ccs
4 x
3,2,1 n
t: toggle bit
c: indicator for more segments
Byte 0
Bit 5-7
ccs / scs
0: Upload seg. Response
scs
1: -
2: -
3: Upload seg. Request
ccs
42
1
reserved
1
0 c
segment data
Bit 4
Bit 3..1
t toggle
n
0: 1. Seg
0: all data valid
starts with 0
(size 7 byte)
1: byte 7 no data
(size 6 byte)
...
7: byte 2 - 7 no data
(size 1 byte)
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
8
8
Bit 0
c
0: more segments to be
uploaded
0: no more segments to be
uploaded