SUN2000-(25KTL, 30KTL)-US
User Manual
Installation Environment Requirements
The SUN2000 must be installed in a well ventilated environment to ensure good heat
dissipation. When installed under direct sunlight, performance de-rate may be initiated due to
additional temperature rise.
Carrier Requirements
Installation Mode Requirements
Issue 09 (2019-06-30)
The installation method and position must be appropriate for the weight and dimensions
of the SUN2000. For details, see
Do not install the SUN2000 in a place where personnel are likely to come into contact
with its enclosure and heat sinks because these parts are extremely hot during operation.
Do not install the SUN2000 in an area that stores flammable or explosive materials.
The carrier where the SUN2000 is installed must be fire-proof.
Do not install the SUN2000 on flammable building materials.
The wall must be solid enough to bear the weight of the SUN2000.
Do not install the SUN2000 on a wall made of gypsum boards or similar materials with
weak sound insulation to avoid noise disturbance in a residential area.
Install the SUN2000 upright or at a maximum back tilt of 15 degrees to facilitate heat
dissipation.
Figure 4-1 Correct installation modes
Do not install the SUN2000 at a front tilt, excessive back tilt, or side tilt, horizonta lly, or
upside down.