SUN2000-(25KTL, 30KTL)-US
User Manual
Parameter
Level-4 OV protection
Level-4 OV protection
time
Level-3 UV protection
Level-3 UV protection
time
Level-4 UV protection
Level-4 UV protection
time
7.2.2.3 Setting Feature Parameters
Procedure
Step 1 Choose Function Menu > Settings > Feature Parameters to access the settings screen.
Figure 7-7 Feature Parameters (special user)
----End
Issue 09 (2019-06-30)
Description
Specifies the level-4 overvoltage
protection threshold.
Specifies the level-4 overvoltage
protection duration.
Specifies the level-3 undervoltage
protection threshold.
Specifies the level-3 undervoltage
protection duration.
Specifies the level-4 undervoltage
protection threshold.
Specifies the level-4 undervoltage
protection duration.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Unit
Value Range
V
[1 x Vn, 1.36 x Vn]
ms
[50, 7200000]
V
[0.15 x Vn, 1 x Vn]
ms
[50, 7200000]
V
[0.15 x Vn, 1 x Vn]
ms
[50, 7200000]