Huawei SUN2000-30KTL-US User Manual page 106

Hide thumbs Also See for SUN2000-30KTL-US:
Table of Contents

Advertisement

SUN2000-(25KTL, 30KTL)-US
User Manual
Figure 7-8 Power Adjustment (special user)
----End
Parameter List
Table 7-5 Parameter description
Parameter
Remote power
schedule
Schedule instruction
valid duration
Maximum active
power
Shutdown at 0%
power limit
Active power
change gradient
Fixed active power
derating
Issue 09 (2019-06-30)
Description
If this parameter is set to Enable, the
SUN2000 responds to the remote
power schedule command. If it is set
to Disable, the SUN2000 does not
respond to the command.
Adjusts the duration within which the
scheduling instruction is valid.
Specifies the output upper threshold
for the maximum active power to
adapt to various market requirements.
If this parameter is set to Enable, the
SUN2000 shuts down after receiving
the 0% power limit instruction. If this
parameter is set to Disable, the
SUN2000 does not shut down after
receiving the 0% power limit
instruction.
Adjusts the change speed of the
SUN2000 active power.
Adjusts the active power output of the
SUN2000 to a fixed value.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Unit
Value Range
N/A
Disable
Enable
s
[0, 86400]
kW
Disable
Enable
N/A
[0.1, Pmax_limit]
%/s
[0.1, 1000]
kW
[0, Pmax]
Pmax represents the maximum
active power.
99

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun2000-25ktl-us

Table of Contents