Setting Power Adjustment Parameters - Huawei SUN2000-50KTL-JPM0 User Manual

Hide thumbs Also See for SUN2000-50KTL-JPM0:
Table of Contents

Advertisement

SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
No.
Parameter
10
Voltage rise
suppression
11
Voltage rise
suppression
reactive
adjustment
point
Voltage rise
12
suppression
active
derating point
13
Soft start
time after
grid failure

7.2.2.4 Setting Power Adjustment Parameters

Procedure
Step 1 Choose Function Menu > Settings > Power Adjustment to access the settings screen.
Issue 01 (2018-09-30)
Description
The standards of certain
countries and regions
require that the SUN2000
should prevent the grid
voltage from rising by
delivering reactive power
and decreasing active
power when the output
voltage exceeds a certain
value.
The standards of certain
countries and regions
require that the SUN2000
must generate a certain
amount of reactive power
when the output voltage
exceeds a certain value.
The standards of certain
countries and regions
require that the active
power of the SUN2000 be
derated according to a
certain gradient when the
output voltage exceeds a
certain value.
Specifies the time for the
power to gradually increase
when the SUN2000 restarts
after the power grid
recovers.
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
N/A
Disable
Enable
%
[100, 115]
%
[100, 115]
s
[20, 800]
7 Man-Machine Interactions
Remarks
N/A
This parameter is
displayed when
Voltage rise
suppression is set
to Enable.
The value of
Voltage rise
suppression active
derating point
must be greater
than that of Voltage
rise suppression
reactive
adjustment point.
N/A
84