SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
Parameter List
No.
Parameter
1
Grid code
2
Isolation
3
Auto start upon
grid recovery
4
Grid connection
duration after
power grid
recovery
5
Grid reconnection
voltage upper limit
6
Grid reconnection
voltage lower limit
7
Grid reconnection
frequency upper
limit
8
Grid reconnection
frequency lower
limit
Issue 01 (2018-09-30)
Vn represents the rated voltage and Fn represents the rated frequency.
Description
Set this parameter based on the grid code
of the country or region where the
SUN2000 is used and the SUN2000
application scenario.
Specifies the working mode of the
SUN2000 according to the grounding
status at the DC side and the connection
status to the grid.
Specifies whether to allow the SUN2000
to automatically start after the power grid
recovers.
Specifies the waiting time for SUN2000
restart after the power grid recovers.
The standards of certain countries and
regions require that the SUN2000 must
not export power to the power grid again
when the grid voltage exceeds the value
of Grid reconnection voltage upper
limit after the SUN2000 shuts down due
to a fault.
The standards of certain countries and
regions require that the SUN2000 must
not export power to the power grid again
when the grid voltage is below the value
of Grid reconnection voltage lower
limit after the SUN2000 shuts down due
to a fault.
The standards of certain countries and
regions require that the SUN2000 must
not export power to the power grid again
when the grid frequency exceeds the
value of Grid reconnection frequency
upper limit after the SUN2000 shuts
down due to a fault.
The standards of certain countries and
regions require that the SUN2000 must
not export power to the power grid again
when the grid frequency is below the
value of Grid reconnection frequency
lower limit after the SUN2000 shuts
down due to a fault.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Unit
Value Range
N/A
N/A
N/A
Input ungrounded,
without TF
Input ungrounded,
with TF
N/A
Disable
Enable
s
[0, 900]
V
[1 x Vn, 1.36 x Vn]
V
[0.45 x Vn, 0.95 x Vn]
Hz
[1 x Fn, 1.12 x Fn]
Hz
[0.85 x Fn, 1 x Fn]
79