SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
No.
Parameter
Description
14
Communic
Specifies the duration
ation
for determining
interruptio
communication
n duration
interruption, and is
used for automatic
shutdown for
protection in case of
communication
interruption.
15
Soft start
Specifies the duration
time
for the power to
gradually increase
when the SUN2000
starts.
OVGR
If this parameter is set
16
linked
to Enable, the
shutdown
SUN2000 shuts down
after receiving the
OVGR signal. If this
parameter is set to
Disable, the
SUN2000 does not
shut down after
receiving the OVGR
signal.
Dry contact
Identifies dry contact
17
function
signals sent from the
SmartLogger.
18
Hibernate
The SUN2000
at night
monitors PV strings at
night. If Hibernate at
night is set to Enable,
the monitoring
function of the
SUN2000 will
hibernate at night,
reducing power
consumption.
Issue 01 (2018-09-30)
Unit
Default
Value
min
30
s
20
N/A
Enable
N/A
NC
N/A
Disable
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Value Range
Remarks
[1, 120]
N/A
[20, 1800]
N/A
Disable
N/A
Enable
Set this parameter to
NC
OVGR for OVGR
OVGR
signals, and set it to
NC for other
signals.
Disable
N/A
Enable