Ex relevant specifications
11 Ex relevant specifications
11.1 Zone 2/22 version
11.1.1 Marking
Transmitter with remote mount design
II 3G Ex ec IIC T4 Gc
II 3D Ex tb IIIC T115°C Dc
T
= -20 ... 50 °C (-4 ... 122 °F)
amb
11.1.2 Safety specifications for inputs and outputs
Power supply circuit
Analog / HART
Output circuit (active):
Digital output (passive):
Digital input (passive):
PROFIBUS DP RS 485
PE current circuit:
PA current circuit:
11.2 Designs for potentially explosive atmospheres in accordance with ATEX and FM
This chapter includes information that must be observed when using the devices in potentially
explosive atmospheres (devices in accordance with ATEX Cat. 1/2 G and 2 D (Zone 1/21, Zone
0/21), FM Cl.1, Div.1/2).
This applies specifically to the mandatory safety instructions, the wiring of the signal and supply
power lines, and the safety specifications from the valid certificates.
Please also remember to comply with the other information in this manual.
Information for safe operation
ATEX
Meters must be installed, commissioned and operated according to ElexV (Standard on
electrical equipment in potentially explosive atmospheres) and EN 60079-14 (Installation of
electrical equipment in potentially explosive atmospheres).
FM
Installations must conform to "Installation of Intrinsically Safe Systems for Hazardous
(Classified) Locations" (ANSI / ISA RP 12.6) and "National Electric Code" (ANSI / NFPA 70
Sections 504 and 505). Comply with the relevant control drawings.
50 - EN
Flowmeter sensor with remote mount
design
II 3G Ex ec IIC T4 Gc
II 3D Ex tb IIIC T150°C Dc
T
= -20 ... 80 °C (-4 ... 176 °F)
amb
T
= -20 ... 150 °C (-4 ... 302 °F)
medium
Non-sparking type of protection Ex ec II
Non-sparking type of protection Ex ec II
Non-sparking type of protection Ex ec II
Non-sparking type of protection Ex ec II
Non-sparking type of protection Ex ec II
Non-sparking type of protection Ex ec II
Non-sparking type of protection Ex ec II
Sensyflow FMT500-IG
Integral mount design
II 3G Ex ec IIC T4 Gc
II 3D Ex tb IIIC T150°C Dc
T
= -20 ... 50 °C (-4 ... 122 °F)
amb
T
= -20 ... 150 °C (-4 ... 302 °F)
medium
U
= 24 V AC / DC ± 20 %, P
n
n
U
= 110 ... 230 V AC / DC ± 10 %, P
n
U
= 30 V
n
U
= 30 V
n
I
≤ 100 mA
max
U
= 30 V
n
U
= < 8 V
n
CI/FMT500-IG-EN
< 20 VA
< 20 VA
n