maximum of 11 characters can be entered.
Comment: Used for commenting; used to explain detailed module information,
a maximum of 21 characters can be entered.
Remote Config. Enable: Used for security setting. When checked, it allows
remote setting of Ether_Config through the internet. This item must be checked
if you want to use the internet setting method mentioned above; it is suggested
to use a password along with this method in order to avoid security leakages.
Please do not check this option if not necessary in order to avoid inappropriate
changes.
Remote Web Access Enable: Used for security setting. When checked, it allows
remote web page operations through the internet. This item must be checked if
you want to use the internet setting method mentioned above; it is suggested
to use a password along with this method in order to avoid security leakages.
Please do not check this option if not necessary in order to avoid inappropriate
changes.
Import, Export: Use the Export function to save all of the module's setting
information, and later on use the Import function to read the Exported file or
file generated with offline editing (please refer to the descriptions in 3.1.8) for
more convenient module data setting.

3.1.3 Operation Mode Setting

Under the General setting page, in addition to setting fields related to the IP address,
there's also a section used to set the operation mode, as shown in the figure below:
Port1 is fixed to be used for the FATEK Server can be used for the editing of ladder
programs or the accessing of data. Port2 is used to support Modbus/TCP or FATEK
client mode. When Port2 is selected to Modbus client mode or Fatek client mode,
the user must also set the "Properties" setting in the Port Mapping setting page
(please refer to the descriptions in chapter 3.1.4).

3.1.4 Access Control

Access Control Setting: Set authorized IP to restrict inappropriate data accessing. To
set authorized IP, you can click the Access Control setting page and the following
screen will appear: