Chapter 2 Application Examples; Application Connections; Setting Plc Communication Parameters - FATEK FBs-1HLC Operation Manuals

Precision load cell module
Hide thumbs Also See for FBs-1HLC:
Table of Contents

Advertisement

Status/Settings register
Address
Name
402305
AD internal value
402307
Display value
SPAN calibration
402567
weight
402561
Max. weight
Calibration error
401793
message

Chapter 2 Application examples

2.1 Application connections

Complete the hardware wiring connection first; please refer to the hardware equipment and
connection scheme in below.
Hardware: FBs-24MC*1, FBs-1HLC*1, and scale*1
1. Connect 1HLC cable to the left (communication) expansion port of PLC.
2. The 4 lines of the scale are connected to EXC+, EXC-, SIG+, and SIG- of 1HLC.
Value of scale analog signal voltage converted for internal calculations of the
scale.
Actual measured weight after specification calibration and weight calibration.
Weight of known standardized weight in calibration.
Set maximum weight of scale and display overload flag if exceeding the max.
weight.
0 : normal
1 : AD abnormal
2 : weight calibration earlier than prerequisite calibration (e.g., SPAN1<ZERO)
3 : weight calibration precision higher than 0.1uV/D
1HLC
8
Description
24V power supply
24MC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents